| 035731967R | Jul 6, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 7, 2026 | POP IN-VIOL | — |
| 1836424 | Jul 6, 2026 | REISSUE#35721363R FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR FPSC DOORS DO NOT SELF-CLOSE PROPERLY AT 5TH FLOOR STAIRCASE A,H.4TH FLR-STAIRCASE A,B.3RD FLR-STAIRCASE H.1ST FLR-MAIN ENT | Aug 7, 2026 | POP/IN-VIO | — |
| 1733407 | Aug 6, 2025 | EXIT DOOR NOT SELF-CLOSING. REISSUE: 35684878X EXIT DOORS NOT SELF-CLOSING. NOTED: OBSERVED ON THE FIRST FLOOR EXIT 8, 5, 10, AND 6. THESE DOORS WERE NOT OPENING AND CLOSING PROPERLY. REMEDY: REPAIR AND/OR REPL | Aug 29, 2025 | POP/IN-VIO | — |
| 035721363R | Aug 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 29, 2025 | POP IN-VIOL | — |
| 035721364Z | Aug 6, 2025 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER:LACK EMERGENCY LIGHT FOR EXITS | Aug 29, 2025 | POP IN-VIOL | — |
| 1732952 | Aug 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-542. NOTED: EMERGENCY EXIT LIGHT DID NOT WORK WHEN TESTED ON 5TH FL | Aug 29, 2025 | POP/IN-VIO | — |
| 035721366M | Aug 6, 2025 | EXIT DOOR NOT SELF-CLOSING | Aug 29, 2025 | POP IN-VIOL | — |
| 1724278 | Aug 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORSMOKE DOORS DO NOT SELF-CLOSE ON 4TH FLR-STAIRCASE(A). 2ND FLR-STAIRCASE(D). INTERIOR CLASSROOM DOORS DO NOT SELF-CLOSE ON 4TH FLR-401, 412, | Aug 29, 2025 | POP/IN-VIO | — |
| 035721365K | Aug 6, 2025 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Aug 29, 2025 | POP IN-VIOL | — |
| 1733402 | Aug 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: DURING INSPECTION IN ELECTRICAL ROOM THERE WAS FIRE STOPPING MISSING IN MULTIPLE. REMEDY: PROVIDE/MAINTAIN FI | Aug 29, 2025 | POP/IN-VIO | — |
| 035684878X | Sep 18, 2024 | EXIT DOOR NOT SELF-CLOSING | Nov 29, 2024 | POP IN-VIOL | — |
| 1730591 | Sep 18, 2024 | REISSUE#35674768X EXIT DOORS NOT SELF-CLOSING.NOTED OBSERVED ON THE FIRST FLOOR EXIT 8,5,10,AND 6 THESE DOORS WERE NOT OPENING AND CLOSING PROPERLY.REM:REPAIR/REPLACE DOOR. | Nov 29, 2024 | POP/IN-VIO | — |
| 035674768X | May 15, 2023 | OPERATION OF CRANE DERRICK W O CERTIFICATE OF ONSITE INSPECTION | Nov 3, 2023 | POP IN-VIOL | — |
| 035674767Y | May 15, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 3, 2023 | POP IN-VIOL | — |
| 1596402 | May 15, 2023 | REISSUE #35654627Y. EXIT DOOR NOT SELF-CLOSING. AT TIME OF INSPECTION I OBSERVED AT 1ST FLOOR EXIT 9 AND 10 EXIT DOOR ARE NOT SELF CLOSING PROPERLY AT THE MAIN ENTRANCE. VIOLATION #36654627Y ISSUE 03/29/2022 FO | Nov 3, 2023 | POP/IN-VIO | — |
| 1728370 | May 15, 2023 | REISSUE #. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED AT 16 5TH FLOOR STAIRWAY "A". EXIT DOOR NOT SELF-CLOSING PROPERLY. VIOLATION #36654628X ISSUED 03/29/2022 FOR V | Nov 3, 2023 | POP/IN-VIO | — |
| 035654628X | Mar 29, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 15, 2022 | POP IN-VIOL | — |
| 1593908 | Mar 29, 2022 | REISSUE #35560747L DATE:4/15/21 EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION.AT THE TIME OF INSPECTION OBSERVED AT 1ST FLOOR EXIT 9 & EXIT 10 DOOR ARE NOT SELF CLOSING PROPERLY IN MAIN ENTRANCE | Jul 15, 2022 | POP/IN-VIO | — |
| 1044746 | Mar 29, 2022 | REISSUED #35560746J DATE:4/15/21 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT TIME OF INSPECTION OBSERVED 5TH FLOOR STAIR "A" EXIT DOOR NOT SELF CLOSING PROPERLY.REMEDY:REPAIR OR REPLACE EXIT DOOR C | Jul 15, 2022 | POP/IN-VIO | — |
| 1272564 | Mar 29, 2022 | REISSUE #35560748N DATE:4/15/21 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC1008.1.8;27-371(J) AT TIME OF INSPECTION OBSERVED KEY CYLINDER LOCKING DEVICES | Jul 15, 2022 | POP/IN-VIO | — |
| 1272606 | Mar 29, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER BC1006.1;27-381 AT TIME OF INSPECTION OBSERVED AT 1ST FLOOR PLAY YARD 1 EMERGENCY LIGHT & 2ND | Jul 15, 2022 | POP/IN-VIO | — |
| 035654626M | Mar 29, 2022 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: USE PROB DOOR HARDWARE | Jul 15, 2022 | POP IN-VIOL | — |
| 035654627Y | Mar 29, 2022 | EXIT DOOR NOT SELF-CLOSING | Jul 15, 2022 | POP IN-VIOL | — |
| 035654629H | Mar 29, 2022 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Jul 15, 2022 | POP IN-VIOL | — |
| 035560747L | Apr 15, 2021 | EXIT DOOR NOT SELF-CLOSING | Jul 16, 2021 | POP IN-VIOL | — |
| 035560748N | Apr 15, 2021 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: USE PROB DOOR HARDWARE | Jul 16, 2021 | POP IN-VIOL | — |
| 1269498 | Apr 15, 2021 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:OBSERVED KEY CYLINDER LOCKING DEVICES INSTALLED ON PANIC BAR/PUSH BAR HARDWARE ON PUS | Jul 16, 2021 | POP/IN-VIO | — |
| 1618106 | Apr 15, 2021 | EXIT DOOR NOT SELF-CLOSING NOTED:OBSERVED EXTERIOR EXIT DOORS AT EXIT#9 IS RACKED AND KNOCKS ON DOOR FRAME REMAINING AJAR EXIT 10 LEFT DOOR DOOR REMAINS WIDE OPEN AND DO NOT SELF CLOSE.REM:REPAIR/REPLACE DOOR. | Jul 16, 2021 | POP/IN-VIO | — |
| 1618104 | Apr 15, 2021 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:OBSERVED AT 5TH FLOOR-STAIR "A" EXTRA AND AT STAIR "H" FIRE PROOF SELF CLOSING DOOR ARE BACKED AND KNACK ON DOOR BUCK ALSO DOORS ARE NOT SELF CLOSING | Jul 16, 2021 | POP/IN-VIO | — |
| 035560746J | Apr 15, 2021 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 16, 2021 | POP IN-VIOL | — |
| 1531070 | Apr 16, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE DAMAGE TO CEILINSG IN ROOMS 501,503,509,511, AND 517 DUE TO WATER PENETRATION FROMR OOF LEAKS REPAIR OR REPLACE | Aug 21, 2020 | POP/IN-VIO | — |
| 1375383 | Apr 16, 2020 | REISSUE #35402330M FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTE AT ROOF LEVEL IN VARIOUS AREAS ROOF LEAKS CAUSING DAMAGE TO CEILINSG IN ROOMS BELOW REPAIR AND OR REPLACE | Aug 21, 2020 | POP/IN-VIO | — |
| 035473385H | Apr 16, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 21, 2020 | POP IN-VIOL | — |
| 035473386J | Apr 16, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 21, 2020 | POP IN-VIOL | — |
| 035473387L | Apr 16, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 21, 2020 | POP IN-VIOL | — |
| 1334966 | Apr 16, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOET AT 1ST FLOOR EXIT #3 DOOR JAM IN DISREPAIR JAM IS CRACKED AND NOT HOLDING HING SCREWS ON DOOR REPAIR AND OR REPLACE | Aug 21, 2020 | POP/IN-VIO | — |
| 035459413P | Dec 9, 2019 | FAILURE TO MAINTAIN BUILDING WALL S OR APPURTENANCES | Jan 31, 2020 | POP IN-VIOL | — |
| 1493225 | Dec 9, 2019 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCE. NOTE AT EXPOSURE#3REAR YARD DEFECTIVE MASONARY ON FACADE. SIDEWALK SHED INSTALLED PERMIT#201203704. SCAFFOLDING PERMIT#201203713. WORK PERMIT#201203697. REMED | Jan 31, 2020 | POP/IN-VIO | — |
| 035459136X | Oct 18, 2019 | FAILURE TO MAINTAIN BUILDING WALL S OR APPURTENANCES | Dec 20, 2019 | POP IN-VIOL | — |
| 1555449 | Oct 18, 2019 | REISSUE #39008937Z.FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCESNOTED:AT TIME OF INSPECTION I OBSERVED AT THE REAR YARD DEFECT IS OVER 9 FOOT HIGH MASONRY FENCE WAY AT REAR YARD OF PUBLIC SCHOOL 177 IS ER | Dec 20, 2019 | POP/IN-VIO | — |
| 0107985635 | Feb 10, 1999 | FAILURE TO SOURCE SEPARATE DESIGNATED RECYCLABLES | Jul 12, 2000 | Written off | — |