| 388589 | Jul 1, 2025 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING. MANY UNITS IN SCHOOL NEED NEW BATTERY, NOT WORKING WHEN TESTED. REMEDY: PROVIDE ADEQUATE POWER EMERGENCY EXIT LIGHTING. | Aug 15, 2025 | POP/IN-VIO | — |
| 1811055 | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ROOF LEVEL ROOFLEAKING AREAS PATCHED HAVE FAILED. PATCHED LIFTED UP AND CRACKING CRA CKS ALL OVER ROOF WATER LEAKS TO AREAS BELOW. ONE BEING ROOM 204 ON AL | Aug 15, 2025 | POP/IN-VIO | — |
| 035721257N | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 035721256L | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 1811060 | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FRONT EXP 1 MAIN ENTRANCE FENCE FULLY RUSTED AWAY MISSING BASE. REMEDY: REPAIR AND/ORREPLACE. | Aug 15, 2025 | POP/IN-VIO | — |
| 1811053 | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ELECTRICAL ROOM014 WATER COMING INTO ROOM FROM BEHIND PANEL ON WALL AND CORNERS. REMEDY: REPAIR AND/OR REPLACE. | Aug 15, 2025 | POP/IN-VIO | — |
| 1811051 | Jul 1, 2025 | FAILIURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EXTERIOR DOOR FRAME RUSTED AND METAL MISSING HOLES IN FRAME. REMEDY: REPAIR AND/OR REPLACE. | Aug 15, 2025 | POP/IN-VIO | — |
| 388143 | Jul 1, 2025 | WORK WITHOUT A PERMIT. IN GYM ELECTRICAL PANEL 3 NEW CIRCUITS INSTALLED RUNNING 3 EXTENSION CORDS ACROSS GYM TO POWER A/C UNIT EACH END AT ELECTRICAL BOX NO PERMITS ON FILE AND NO WORK DONE TO CODE. REMEDY: OBT | Aug 15, 2025 | POP/IN-VIO | — |
| 035721255J | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 035721254H | Jul 1, 2025 | WORK WITHOUT A PERMIT | Aug 15, 2025 | POP IN-VIOL | — |
| 035721258P | Jul 1, 2025 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING | Aug 15, 2025 | POP IN-VIOL | — |
| 035721253X | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 035721252Y | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 035721251M | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 15, 2025 | POP IN-VIOL | — |
| 1811052 | Jul 1, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. GAS METER ROOM,RIGHT WALL CONCRETE COLUMN FRACTURE AND BREAKING POINT. REMEDY: REPAIRAND/OR REPLACE. | Aug 15, 2025 | POP/IN-VIO | — |
| 1811054 | Jul 1, 2025 | FAILURET TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FACADE AROUND BUILDING MORTAR MISSING AND CRACKS ALONG WITH CRACKS IN THE PARAPET SHIFTED AND GAPS OPEN, CAP STONE CRACKS AND MORTAR MISSING IN FRON STONE | Aug 15, 2025 | POP/IN-VIO | — |
| 035679045P | May 7, 2024 | EXIT DOOR NOT SELF-CLOSING | Jun 20, 2024 | POP IN-VIOL | — |
| 1493385 | May 7, 2024 | EXIT DOOR NOT SELF-CLOSING. NOTED: EXIT 2 THE DOOR ON THE LEFT IS NOT CLOSING PROPERLY, THE DOOR IS HITTING ON THE SADDLE. REMEDY: REPAIR/REPLACE DOOR. | Jun 20, 2024 | POP/IN-VIO | — |
| 048377202H | Apr 18, 2024 | IMPROPER DISPOSAL - 1ST OFFENSE | Jul 9, 2024 | Defaulted (did not respond) | $75.00 |
| 035672603Z | Feb 17, 2023 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Jun 7, 2023 | POP IN-VIOL | — |
| 1652407 | Feb 17, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC1006.1; 27-381 NOTED:ON 2ND FL CORRIDOR TWO LIGHTS IN CAFETERIA TWO LIGHT ALL THESE LIGHTS N | Jun 7, 2023 | POP/IN-VIO | — |
| 342512 | May 20, 2021 | EXIT DOOR NOT SELF CLOSING PROPERLY AT 1ST FL EXIT 7 OUTSIDE EXIT DOOR2 EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION. REMEDY: REPAIR/REPLACE DOOR. | Oct 20, 2021 | POP/IN-VIO | — |
| 035561370P | May 20, 2021 | EXIT DOOR NOT SELF-CLOSING | Oct 20, 2021 | POP IN-VIOL | — |
| 035561369H | May 20, 2021 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Oct 20, 2021 | POP IN-VIOL | — |
| 1513281 | May 20, 2021 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1;27-381. IN BASEMENT LEVEL IN CAFETERIA IN 5 PLACE EACH PLACE 2 LIGHT & IN 1ST FL GYM 6 P | Oct 20, 2021 | POP/IN-VIO | — |
| 1476042 | Jun 3, 2020 | REISSUE#35433893H NOTED AT GYMNASIUM LEFT EXIT STAIR E 1ST FLOOR STAIR C AND D AND SMOKE BY THE MAIN ENTRANCE THE EXIT DOORS ARE NOT WORKING PROPERLY REPAIR AND OR REPLACE DOOR | Jul 6, 2020 | POP/IN-VIO | — |
| 035495951K | Jun 3, 2020 | EXIT DOOR NOT SELF-CLOSING | Jul 6, 2020 | POP IN-VIOL | — |
| 035495955H | Jun 3, 2020 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Jul 6, 2020 | POP IN-VIOL | — |
| 1476048 | Jun 3, 2020 | REISSUE #35433892X NOTED AT EXPOSURE 3(REAR OF BUILDING WATER PENETRATION ABOVE THE 2ND FLOOR WINDOW MAINLY AT ROOM 204 REPAIR AND OR REPLACCE | Jul 6, 2020 | POP/IN-VIO | — |
| 035495954X | Jun 3, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 6, 2020 | POP IN-VIOL | — |
| 035495952M | Jun 3, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 6, 2020 | POP IN-VIOL | — |
| 1476086 | Jun 3, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ULLIMUNATIONFOR EXITS ,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006;1,27-381.NOTED AT THE GYMNASIUM BY STAIR E (#20) INSIDE THE GYMANSIUM AT MAIN ENTRAN | Jul 6, 2020 | POP/IN-VIO | — |
| 035495953Y | Jun 3, 2020 | MISCELLANEOUS VIOLATIONS | Jul 6, 2020 | POP IN-VIOL | — |
| 1476058 | Jun 3, 2020 | 28-301.1-REISSUE#35334190H NOTED AT THE GAS METER ROOM DOES NOT HAVE A FRESH AIR OR MECHANICAL COMPLY WITH A NOTICE OF VIOLATION | Jul 6, 2020 | POP/IN-VIO | — |
| 1476062 | Jun 3, 2020 | FAILURE TO MAINTAIN BUILDINGIN CODE COMPLIANT MANNER NOTED AT STAIR A ROOF DOOR AND 202;THE DOORS ARE NOT WORKING PROPERLY REPAIR AND OR REPLACE | Jul 6, 2020 | POP/IN-VIO | — |
| 1204406 | Nov 16, 2016 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER;LACK OF EMERGENCY LIGHTING FOR EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-542.REM:@1ST FLR, GYM AREA AND THE PUBLIC CORRDOR INOPERATIVE EMERGENCY LIG | Jan 30, 2017 | POP/IN-VIO | — |
| 035221628M | Nov 16, 2016 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER:LACK EMERGENCY LIGHT FOR EXITS | Jan 30, 2017 | POP IN-VIOL | — |
| 1462718 | Sep 22, 2011 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER. NOTE: AT CELLAR LEVEL OF ABOVE PREMISES THERE IS NO FRESH AIR VENT IN GAS METER ROOM. REMEDY: PROVIDE FRESH AIR VENT IN GAS METER ROOM. | Mar 26, 2012 | Defaulted (did not respond) | — |
| 1525087 | Sep 22, 2011 | OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION. NOTE: LUNCH ROOM IN CELLAR IS BEING USED AS A P.A. W/SEATING FOR WELL OVER 100 PERSONS. REMEDY: OBTAIN A PLACE OF ASSEMBLY CERT OF OPERAT | Mar 26, 2012 | Defaulted (did not respond) | — |
| 034927667N | Sep 22, 2011 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Mar 26, 2012 | Defaulted (did not respond) | — |
| 034927668P | Sep 22, 2011 | OPERATION OF PLACE OF ASSEMBLY W O A CURRENT CERTIFICATE OF OPERATION | Mar 26, 2012 | Defaulted (did not respond) | — |
| 1458043 | Jun 3, 1991 | WORK WITHOUT A PERMIT BALCONY CONVERTED T ART ROOM ENCLOSED THE SIDES(3SIDES)WITH SHEETROCK THE EXTERIOR SIDE IS MADE OF CONC BLOCK W/C IS EXISTING BEFORE THE CONVERSION APPROX SIZE OF BALCONY IS 12X30' REMEDY: | Jul 15, 1991 | Settled by stipulation | — |
| 034058829P | Jun 3, 1991 | WORK WITHOUT A PERMIT. | Jul 15, 1991 | Settled by stipulation | — |