| 1834570 | Jun 15, 2026 | REISSUE#35717364R DATE OF ISSUE:05.06.2026 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.AT THE TIME OF INSPECTION OBSERV | Jul 20, 2026 | POP/IN-VIO | — |
| 1834575 | Jun 15, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT 1ST FLOOR LEVEL ELECTRICAL ROOM,LOT OF STORAGE BOXES,LADDERS,FURNITURES IN SIDE ELECTRICAL ROOM.REM:KIP CLEAN ELECTRICAL ROOM ALL THE TIME. | Jul 20, 2026 | POP/IN-VIO | — |
| 035734334K | Jun 15, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 20, 2026 | POP IN-VIOL | — |
| 035734333Z | Jun 15, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 20, 2026 | POP IN-VIOL | — |
| 035734332R | Jun 15, 2026 | EXIT DOOR NOT SELF-CLOSING | Jul 20, 2026 | POP IN-VIOL | — |
| 035734331P | Jun 15, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jul 20, 2026 | POP IN-VIOL | — |
| 035734330N | Jun 15, 2026 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS | Jul 20, 2026 | POP IN-VIOL | — |
| 1834574 | Jun 15, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT THE TIME OF INSPECTION OBSERVED AND NOTED FOR DIFECTIVE HARDWARE DOOR CLOSURE OR HINGES DOORS ARE NOT SELF-CLOSING PROPERLY AT 1ST FL MAIN ENT.INSIDE 5 E | Jul 20, 2026 | POP/IN-VIO | — |
| 1834572 | Jun 15, 2026 | REISSUE#35717363P DATE OF ISSUE:05.06.2025 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT THE TIME OF INSPECTION OBSERVED AND NOTED AT THE TIME OF INSPECTION THE ROLLING GATE AT THE YARD ENTRY FROM TH | Jul 20, 2026 | POP/IN-VIO | — |
| 1834573 | Jun 15, 2026 | REISSUE:35717362N DATE OF ISSUE:05.06.2025 EXIT DOOR OUTSIDE NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION.AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 1ST FLOOR EXIT-3 OUTSIDE TWO EXIT DOORS ARE NOT C | Jul 20, 2026 | POP/IN-VIO | — |
| 1442477 | May 6, 2025 | RE-ISSUE #35672948Y. EXIT DOORS NOT SELF-CLOSING. NOT SEVERAL DOOR THROUGHOUT THE SCHOOL NEED TO BE REPLACED. INCLUDING AUDITORIUM, SMOKE AND CORRIDOR AND SMOKE EXTERIOR EXIT DOORS. OLD, DETERIORATED, BENT, WAR | Jun 27, 2025 | POP/IN-VIO | — |
| 1442501 | May 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS AS PER BC 1006.1; 27-381. NOTED: THERE WERE SEVERAL EMERGENCY LIGHTS SCATTERED AROUND THE SCHO | Jun 27, 2025 | POP/IN-VIO | — |
| 1824338 | May 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION, THE ELECTRIC METER ROOM WAS CLUTTERED WITH EXCESSIVE STORAGE. MOST OF THE ITEMS WERE COMBUSTABLE. REMEDY: REMOVE ALL STORAGE | Jun 27, 2025 | POP/IN-VIO | — |
| 035717362N | May 6, 2025 | EXIT DOOR NOT SELF-CLOSING | Jun 27, 2025 | POP IN-VIOL | — |
| 035717363P | May 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jun 27, 2025 | POP IN-VIOL | — |
| 035717364R | May 6, 2025 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS | Jun 27, 2025 | POP IN-VIOL | — |
| 035717365Z | May 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jun 27, 2025 | POP IN-VIOL | — |
| 1442480 | May 6, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: THE ROLLING GATE AT THE YARD ENTRY FROM THE 44TH STREET SIDE IS BENT, BROKEN, MISSING COMPONENTS AND NOT OPERATING AS IT SHOULD. VERY DIFFICULT TO O | Jun 27, 2025 | POP/IN-VIO | — |
| 1624953 | Jun 7, 2023 | REISSUE #35663155J EXIT DOOR NOT SELF CLOSING. DO AND FRAME AND DOORS BEYOND REPAIR NEED NEW DOORS STAIRS BY 342 STAIR D BY 345 2ND FL SMOKE BY 233 SMOKE BY 229 AUDITORIUM. REMEDY: REPAIR/REPLACE DOOR | Oct 11, 2023 | POP/IN-VIO | — |
| 035672948Y | Jun 7, 2023 | EXIT DOOR NOT SELF-CLOSING | Oct 11, 2023 | POP IN-VIOL | — |
| 035663154H | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 2, 2022 | POP IN-VIOL | — |
| 035663155J | Jun 8, 2022 | EXIT DOOR NOT SELF-CLOSING | Nov 2, 2022 | POP IN-VIOL | — |
| 035663156L | Jun 8, 2022 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Nov 2, 2022 | POP IN-VIOL | — |
| 035663158P | Jun 8, 2022 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Nov 2, 2022 | POP IN-VIOL | — |
| 1092963 | Jun 8, 2022 | EXIT DOOR NOT SELF-CLOSING.NOTED:AT 5TH FLOOR LEVEL STAIR BY 523,4TH FLOOR SMOKE AT STAIR C BY 442 STAIR D BY 445 3RD FLOOR SMOKE BY 301 STAIR C BY 342 STAIR D BY 345 2ND FLOOR SMOKE BY 233 SMOKE BY 229 AUDITOR | Nov 2, 2022 | POP/IN-VIO | — |
| 18038 | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER;NO FIRE STOPPING PER BC 712.3;27-345.NOTED:GAS METER ROOM AT CELLAR LEVEL HAS SECTIONS ON CEILING W/O FIRE PROOFING MATERIAL | Nov 2, 2022 | POP/IN-VIO | — |
| 1424656 | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1;27-381 NOTED:AT 5TH FLOOR LEVEL GYMNASIUM OUTSIDE STAIRWELL D (EXIT SIGN) AUDITORIUM | Nov 2, 2022 | POP/IN-VIO | — |
| 1674110 | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:DOORS TO ROOM 301 & 323 NOT WORKING PROPERLY.REMEDY:REPAIR AND/OR REPLACE. | Nov 2, 2022 | POP/IN-VIO | — |
| 1235490 | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 1ST FLOOR LEVEL ELECTRICAL METER ROOM #127 HAS EXCESSIVE STORAGE OF BOXES LADDERS SUPPLIES EQUIPMENT FLAMMABLE LIQUIDS & OTHER MISC ITEMS & COMBUST | Nov 2, 2022 | POP/IN-VIO | — |
| 035663157N | Jun 8, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 2, 2022 | POP IN-VIOL | — |
| 035490799M | May 27, 2020 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Jul 6, 2020 | POP IN-VIOL | — |
| 1480856 | May 27, 2020 | REISSUED#35442618H(7/22/19)FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATE EXITS @ 5TH GLOOR STAIR C,4TH FLOOR STAIR D,GYMNASIUM,CAFETERIA & MULTI PURPOSE ROOM. REMEDY: REPAIR &/OR REPLACE LIGHTIN | Jul 6, 2020 | POP/IN-VIO | — |
| 1072278 | Feb 11, 2020 | UPON INSPECTION DEVICE WAS FOUND TO BE OUT OF SERVICE. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB FOR FULL INSPECTION. | Feb 21, 2020 | POP/IN-VIO | — |
| 039017352H | Feb 11, 2020 | FAILURE TO MAINTAIN ELEVATOR OR CONVEYING SYSTEM | Feb 21, 2020 | POP IN-VIOL | — |
| 0196006407 | Jul 17, 2017 | DIRTY SIDEWALK DIRTY AREA | Aug 29, 2017 | POP IN-VIOL | — |
| 971180 | Feb 19, 2010 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS NOTED:SUPPORTED SCAFFOLD ERECTED UNDER PERMIT 302136490,CONTRARY TO APPROVED PLANS.REMEDY:CONFORM TO APPROVED PLANS | Apr 12, 2010 | Found in violation | — |
| 703837 | Feb 19, 2010 | FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER NOTED:ON 2/2/10 A SWO#4137 WAS ISSUED FOR UNSAFE CONDITION AND NO APPROVED PLANS FOR THE ERECTION OF SUPPORTED SCAFFOLD OVER 40FT, CONTINUED TO WORK ON ERECTI | Apr 12, 2010 | Found in violation | — |
| 820807 | Feb 19, 2010 | FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER NOTED:S&N BUILDERS INC, ALLOW METROPOLITAN BRIDGE & SCAFF CO TO CONTINUE.TO ERECT SUPPORTED SCAFFOLD KNOWLY THAT A SWO#4137 WAS IN PLACE ON THE JOB SITE | Apr 12, 2010 | Found in violation | — |
| 034821446Y | Feb 19, 2010 | WORK DOES NOT CONFORM TO APPROVED CONST. DOCUMENTS AND/OR APPROVED AME | Apr 12, 2010 | Found in violation | — |
| 034821447X | Feb 19, 2010 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER | Apr 12, 2010 | Found in violation | — |
| 034821445M | Feb 19, 2010 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER | Apr 12, 2010 | Found in violation | — |
| 034821192N | Feb 2, 2010 | SIDEWALK SHED DOES NOT MEET CODE SPECIFICATIONS | Oct 25, 2010 | Written off | — |
| 034821193P | Feb 2, 2010 | FAILURE TO PROVIDE APPROVED ACCEPTED PLANS AT JOB SITE AT TIME OF INSP | Oct 25, 2010 | Written off | — |
| 1472575 | Feb 2, 2010 | FOOTINGS & ANCHORAGE FOR EVERY SCAFFOLD SHALL BE SOUND & RIGID.CAPABLEOF CARRYING THE MAXIMUM LOAD W/O EXCESSIVE SETTLEMENT OR DEFORMATION.NOTED:UNSTABLE FOOTING FOR PIPE SCAFFOLD ERECTED AT EXPOSURE #2 OVER A | Oct 25, 2010 | Written off | — |
| 1472569 | Feb 2, 2010 | FAILURE TO PROVIDE APPROVED/ACCEPTED PLANS AT JOB SITE AT TIME OF INSPECTION.NOTED:AT TIME OF INSPECTION, NO APPROVED PLANS ON SITE FOR ERECTION,NO APPROVED PLANS ON SITE FOR ERECTION OF SUPPORTED SCAFFOLD FILE | Oct 25, 2010 | Written off | — |
| 1472568 | Feb 2, 2010 | SIDEWALK SHED DOES NOT MEET CODE SPECIFICATION.NOTED:SIDEWALK SHED ERECTED UNDER PERMIT 302136506 IS OBSTRUCTING PEDESTRIAN CROSSING SIGNS AT 43 ST,44ST CORNERS ON 7 AVE..REMEDY:CONFORM SHED TO CODE SPECIFICATI | Oct 25, 2010 | Written off | — |
| 034821194R | Feb 2, 2010 | MISCELLANEOUS VIOLATIONS | Oct 25, 2010 | Written off | — |
| 010898221H | Jun 14, 2005 | FAILED TO PROVIDE FIREPROOF DOOR WINDOW | Aug 2, 2005 | Pending | — |
| 0135596634 | May 24, 2003 | DIRTY SIDEWALK | Jun 26, 2003 | Written off | — |
| 443435 | Dec 12, 2000 | FAILURE TO MAINTAIN. NOTE: AT THE NORTH/WEST CORNER(7 AVE,43 ST) A 24' SECTION OF PLYWOOD SIDEWALK SHED ENCLOSURE APPROX. 100'SQ. HAS FALLENTO THE PUBLIC SIDEWALK & STREET. NOTE: STOP ALL OTHER CONSTRUCTION WOR | Jan 29, 2001 | Defaulted (did not respond) | — |
| 034210299K | Apr 27, 1999 | FAILURE TO OBTAIN A PERMIT FOR TEMPORARY CONSTRUCTION. | Jun 14, 1999 | Written off | — |
| 21070 | Apr 27, 1999 | FAILURE TO MAINTAIN, PERMIT FOR SIDEWALK SHED HAS BEEN EXPIRED, PERMITNUMBER 300405210 FOR SIDEWALK SHED FOR BUILDING PERMIT EXPIRED. REMEDY: OBTAIN RENEWAL FOR EXPIRED PERMIT. | Jun 14, 1999 | Written off | — |
| 148580 | Oct 11, 1995 | FAILURE TO MAINTAIN EXTERIOR WALLS. STONE WORK OVER 5TH FLOOR WINDOWS ALONG WEST ELEV. (7 AVE) AND EAST ELEV. (COURT YARD) IS CRACKED IN MANY PLACES, CAUSING LEAKS INTO THE CLASSROOMS. REMEDY: MAKE NECESSARY RE | Dec 4, 1995 | Written off | — |
| 148823 | Oct 11, 1995 | FAILURE TO MAINTAIN EXTERIOR WALLS-(A) MAINENTRANCE ON 7 AVE, THE LIMESTONE IS BROKEN AND CRACKED, NEEDS REPAIR AND POINTING. (B) STONE WORK AROUND CLASSROOM WINDOWS NEEDS REPAIR AND POINTING. REMEDY: MAKE REQU | Dec 4, 1995 | Written off | — |
| 149154 | Oct 11, 1995 | FAILURE TO MAINTAIN CHIMNEY- MASONRY REQUIRES REPAIRS AND POINTING NEAR TOP OF STACK. REMEDY: MAKE REQUIRED REPAIRS TO THE SATISFACTION OF THIS DEPARTMENT. | Dec 4, 1995 | Written off | — |
| 149155 | Oct 11, 1995 | FAILURE TO MAINTAIN ROOF. FIFTH FLOOR CLASSROOM CEILINGS, PAINT IS PEELING BECAUSE OF DAMPNESS. SOME PLASTER CEILING ARE CRACKED. PLASTER IS CRACKED AND MISSING, CAUSING HOLES OVER WINDOWS IN SOME CLASSROOMS. R | Dec 4, 1995 | Written off | — |
| 125974 | Dec 21, 1994 | SIDEWALK SHED DOES NOT MEET BUILDING CODE SPECIFICATONS. DEFECT IS NO LIGHTS. REMEDY: CONFORM SHED TO BUILDING CODE SPECIFICATIONS. | Jun 5, 1995 | Found in violation | — |