| 1726713 | Feb 26, 2024 | REISSUE: 35671654Y-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT ROOF LEVEL TAR PAPER LIFTING UP. ALOWING WATER TO PENETRATE. REMEDY: COMPLY WITH CODE. | Apr 22, 2024 | POP/IN-VIO | — |
| 1726718 | Feb 26, 2024 | REISSUE: 35671651Z-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: CAFETERIA CEILING TILES ARE INDISREPAIR. LOOSE TILES. REMEDY: COMPLY WITH CODE. | Apr 22, 2024 | POP/IN-VIO | — |
| 035672446Y | Feb 26, 2024 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Apr 22, 2024 | POP IN-VIOL | — |
| 035672447X | Feb 26, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Apr 22, 2024 | POP IN-VIOL | — |
| 035672448H | Feb 26, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Apr 22, 2024 | POP IN-VIOL | — |
| 1634871 | Feb 26, 2024 | REISSUE: 35671655X-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC/DOB: 27-381. EXIT LIGHTS NOT WORKING PROPERLY AT CORRIDORS. REMEDY: | Apr 22, 2024 | POP/IN-VIO | — |
| 035671656H | Feb 3, 2023 | EXIT DOOR NOT SELF-CLOSING | May 10, 2023 | POP IN-VIOL | — |
| 035671655X | Feb 3, 2023 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | May 10, 2023 | POP IN-VIOL | — |
| 1617227 | Feb 3, 2023 | REISSUE#35650685Y 3/24/2022.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC712.3,27-345.NOTED OBSERVED DURING INSPECTION OF GAS METER ROOM,PIPES PENETRATED THROUGH BLOCK WALL WITH | May 10, 2023 | POP/IN-VIO | — |
| 1697293 | Feb 3, 2023 | EXIT DOOR NOT SELF-CLOSING.NOTED OBSERVED DURING INSPECTION OF MAIN ENTRANCE EXTERIOR DOORS,THERE WERE NOT OPERATING DUE TO DEFECTIVE HARDWARE.REMEDY:REPAIR AND/OR REPLACE DOOR. | May 10, 2023 | POP/IN-VIO | — |
| 1634813 | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC1006.1,27-381.NOTED OBSERVED DURING INSPECTION OF EMERGENCY LIGHTS IN OFFICE PACK 6 FOR LIG | May 10, 2023 | POP/IN-VIO | — |
| 1697292 | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED DURING INSPECTION OF FIRE PROOF SELF-CLOSING DOORS ON 1ST FL EXIT 9,4,GYM ENTRANCE DOOR,STAIR D AND 2ND FL STAIR D WERE NOT OPERATIONAL DUE T | May 10, 2023 | POP/IN-VIO | — |
| 1713842 | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED DURING INSPECTION OF ROOF WHERE PARAPET MEETS ROOF FACING COURTYARD HASDETACHED/RIPPED EXPOSING SHEATHING UNDERNEATH.REMEDY:REPAIR AND/OR REP | May 10, 2023 | POP/IN-VIO | — |
| 1713838 | Feb 3, 2023 | REISSUE#35650686X 3/24/2022.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED DURING INSPECTION OF CAFETERIA,CEILING TILES ARE IN DISREPAIR,MISSING,OR BROKEN.REMEDY:REPAIR AND/OR REPAIR. | May 10, 2023 | POP/IN-VIO | — |
| 035671651Z | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | May 10, 2023 | POP IN-VIOL | — |
| 035671652K | Feb 3, 2023 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | May 10, 2023 | POP IN-VIOL | — |
| 035671653M | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | May 10, 2023 | POP IN-VIOL | — |
| 035671654Y | Feb 3, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | May 10, 2023 | POP IN-VIOL | — |
| 035650684M | Mar 24, 2022 | EXIT DOOR NOT SELF-CLOSING | Sep 14, 2022 | POP IN-VIOL | — |
| 1634927 | Mar 24, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006-1; 27-381 NOTED:OBSERVED EXISTING EMERGENCY LIGHTS AT GYM(2 LIGHTS) AUDITORIUM(LEFT RE | Sep 14, 2022 | POP/IN-VIO | — |
| 035650686X | Mar 24, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 14, 2022 | POP IN-VIOL | — |
| 035650685Y | Mar 24, 2022 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Sep 14, 2022 | POP IN-VIOL | — |
| 1613088 | Mar 24, 2022 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345.NOTED:PENETRATING THRU CMU BLOCK WALL W/NO FIRESTOPPING PROVIDED.PROVIDE/MAINTAIN FIRESTOPPING. | Sep 14, 2022 | POP/IN-VIO | — |
| 1713385 | Mar 24, 2022 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:OBSERVED@CAFETERIA-ACOUSTICAL CEILING TILES LOOSE@VARIOUS LOCATIONS,MISSING&DETERIORATED THRUOUT ENTIRE CAFETERIA (CONCEALED-Z-TILES).REPAIR &OR REPLACE | Sep 14, 2022 | POP/IN-VIO | — |
| 1634928 | Mar 24, 2022 | EXIT DOOR NOT SELFCLOSING.NOTED:OBSERVED EXTERIOR EXIT DOORS@EXIT4/5 MIDDLE DOOR,KITCHEN EXIT,SIDE EXIT@BOILER RM DONT SELFCLOSE DUE TO DOORS BEING RACKED (BOILER RM/4/5)&MISSING HARDWARE(KITCHEN).REPAIR/REPLAC | Sep 14, 2022 | POP/IN-VIO | — |
| 035650683K | Mar 24, 2022 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Sep 14, 2022 | POP IN-VIOL | — |
| 035473492N | Apr 28, 2020 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Oct 14, 2020 | POP IN-VIOL | — |
| 1516300 | Apr 28, 2020 | REISSUE#35423105Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3;27-345.NOTED:AT CELLAR LEVEL,GAS METERROOM AND ELECTRICAL ROOM MISSING FIRE STOPPING AROUND CONDUITS.REM:PRO | Oct 14, 2020 | POP/IN-VIO | — |
| 1568216 | Jan 10, 2017 | UNLAWFUL ACTS. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. PS307K, REF ECB 35160064J FAILURE TO REMOVE, AND CERTIFY SAID VIOLA TION. RMDY: COMPLY WITH COMMISSIONER'S ORDER. | May 3, 2017 | Found in violation | — |
| 035204176X | Jan 10, 2017 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER | May 3, 2017 | Found in violation | — |
| 035160065L | Aug 15, 2016 | FAIL TO PROV EFF ELECT CONT FOR METAL RACEWAYS ENCLOSURES CABLE ARMOR | Jan 18, 2017 | Found in violation | — |
| 035160064J | Aug 15, 2016 | FAILURE TO GROUND ELECTRICAL SYSTEMS | Jan 18, 2017 | Written off | — |
| 1318422 | Aug 15, 2016 | FAIL TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS/ENCLOSURES, CABLE ARMOUR.OBSERVED METAL RACEWAYS CONTINUITY OF GROUND TO CIRCUIT BREAKERS PANEL HAS NOT BEEN PROVIDED(ROMEX)USED TRUOGH PIPE | Jan 18, 2017 | Found in violation | — |
| 035160066N | Aug 15, 2016 | FAIL TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER GFCI PROTECTION | Dec 19, 2016 | Found in violation | — |
| 628939 | Aug 15, 2016 | FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERPRETER(GFCI)PROTECTION ASREQUIRED.OBSERVED THAT NO GFCI PROTECTION FOR SIDE WALK SHED HAD BEEN INSTALLED.HAZARDOUS AND DANGEROUS.REMEDY INSTALL GFCI PROTECTION | Dec 19, 2016 | Found in violation | — |
| 926016 | Aug 15, 2016 | FAILURE TO GROUND ELECTRICAL SYSTEMS.NON CURRENT CAUSING ELECTRICAL CONDUCTIVE MATERIAL (SIDEWALK SHED)IS NOT GROUNDED HAZARDOUS AND DANGEROUS.REMEDY PROVIDE GROUNDING. | Jan 18, 2017 | Written off | — |
| 1324874 | Aug 12, 2010 | CONVERTED STORAGE ROOM INTO OFFICE WITH NO VENTILATION,MISSING LINTEL OVER DOORWAY,STORAGE OF COMBUSTIBLE LIQUIDS ROOM 128. REMEDY: REMOVE ALL COMBUSTIBLE LIQUIDS,INSTALL F.A.I./VENTILATION,LINTEL,& CARBON | Sep 13, 2010 | Written off | — |
| 034870350K | Aug 12, 2010 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 13, 2010 | Written off | — |
| 449102 | Apr 29, 1999 | FAILURE TO MAINTAIN DEFECT ENTIRE FENCE AT PERMIZ BUSTEDDAMAGED AT REAR PARKING LOT PAVED PLAYGROUND SINK HOLES DANERGOUS PARAPET OVER LOWERROOF LEVEL TO BE RAISED TO REQUIRED HEIGHT 48 REMEDY OTBAIN PERMIT MAK | Aug 16, 1999 | Defaulted (did not respond) | — |