| 1826302 | Aug 26, 2026 | DUE TO WORK PERFORMED UNDER POR CERT ALT 2 JOB# 220669630 EXPIRED ON 09/15/2019, WALLS HAVE ERECTED OBSTRUCTING SPRINKLER COVERAGE., REPAIR AND/REPLACE | Oct 30, 2026 | Pending | $2,500.00 |
| 1826303 | Aug 26, 2026 | ATOI OBSERVED GAS PIPING AND COMPONENTS WITHIN THE FIRE PUMP ROOM NO GAS PIPING IS ALOUD IN THE FIRE PUMP ROOM CONTRARY TO . BC 913.2.1 PROVIDES THAT REFRIGERANTS, GAS PIPING, GAS-CONSUMING DEVICES, GAS METERS, | Oct 30, 2026 | Pending | $2,500.00 |
| 1844978 | Aug 25, 2026 | CLASS 2: 1. EMERGENCY PHONE INOPERATIVE, FAILING REQUIRED TWO-WAY COMMUNICATION FOR PASSENGER ASSISTANCE. AS PER ASME A17.1 2.27. REMEDY: REPAIR EMERGENCY PHONE AND VERIFY CLEAR, RELIABLE TWO-WAY COMMUNICATION. | Oct 30, 2026 | Pending | $625.00 |
| 1653524 | Aug 25, 2026 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM IT EQUIPMENT , CAMERA EQUIPMENT IS INSTALLED. ALL ELECTRICAL ROOMS AND CLOSET SHALL BE DEDICATED A | Oct 30, 2026 | Pending | $1,200.00 |
| 012173575J | Nov 5, 2025 | FIRE PROTECTION SYSTEMS:FAIL TO PREVENT UNNECESSARY UNWARRANTED ALARMS | Jun 18, 2026 | Found in violation | $750.00 |
| 1296431 | Aug 21, 2025 | OBSERVED GAS LINE IN FIRE PUMP ROOM IN BASEMENT WHICH IS CONTRARY TO CODE SECTION FGC 404.3 (3), REPAIR AND/OR REPLACE | Jun 5, 2026 | Found in violation | $1,250.00 |
| 1296440 | Aug 21, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE AT TIME OF INSPECTION OBSERVED HOLE PENETRATIONS AT GROUND FLOOR AND BASEMENT LEVE | Jun 5, 2026 | Found in violation | $2,500.00 |
| 039157966R | Aug 21, 2025 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FIRE STOPPING | Jun 5, 2026 | Found in violation | $2,500.00 |
| 014201799R | Aug 21, 2025 | RECORDKEEPING | Apr 30, 2026 | Found in violation | $2,400.00 |
| 039157965P | Aug 21, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jun 5, 2026 | Found in violation | $1,250.00 |
| 049215370L | Jul 11, 2025 | FAILURE TO CLEAN 18 INCHES INTO STREET | Nov 18, 2025 | Pending | — |
| 014178978J | Mar 27, 2025 | CERTIFICATES OF FITNESS AND CERTIFICATES OF QUALIFICATION | Aug 28, 2025 | Found in violation | — |
| 014145693P | Sep 10, 2024 | INSPECTION AND TESTING | Apr 17, 2025 | Found in violation | — |
| 014145740Z | Sep 10, 2024 | INSPECTION AND TESTING | Apr 17, 2025 | Found in violation | — |
| 014145717K | Sep 10, 2024 | AFFIDAVITS, DESIGN INSTALLATION DOCUMENTS, AND OTHER DOCUMENTATION | Jul 17, 2025 | Found in violation | $1,475.00 |
| 039124210X | Sep 6, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Jan 16, 2026 | Found in violation | — |
| 1704071 | Sep 6, 2024 | OBSERVED PAINTED SPRINKLER CAPS( CONCEALED HEADS) THROUGHOUT BUILDING. AS PER 102.3 OF THE PLUMBING CODE INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION | Jan 16, 2026 | Found in violation | — |
| 012154569J | Aug 9, 2024 | FIRE PROTECTION SYSTEMS:FAIL TO PREVENT UNNECESSARY UNWARRANTED ALARMS | Feb 27, 2025 | Found in violation | — |
| 048114393P | Nov 18, 2023 | FAILURE TO CLEAN 18 INCHES INTO STREET | Feb 20, 2024 | Defaulted (did not respond) | — |
| 047646101P | Nov 17, 2022 | FAILURE TO CLEAN 18 INCHES INTO STREET | Feb 15, 2023 | Pending | — |
| 039049010Y | Oct 8, 2021 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER: SERVICE EQUIPMENT - BOILER | Dec 3, 2021 | Settled by stipulation | — |
| 1581355 | Oct 8, 2021 | NEED TO CHANGE DRAFT STAT, NEED TO CHANGE ACID ROCKS IN FILTER | Dec 3, 2021 | Settled by stipulation | — |
| 1581344 | Oct 8, 2021 | DRAFT STAT NEED TO BE CHANGED, ROCKS THAT ARE IN FILTER NEED TO BE CHANGED, NEED TO FIX DRAIN FROM ACID FILTER TO DRAIN. | Dec 3, 2021 | Settled by stipulation | — |
| 039049011X | Oct 8, 2021 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER: SERVICE EQUIPMENT - BOILER | Dec 3, 2021 | Settled by stipulation | — |
| 047274523K | Aug 14, 2021 | FAILURE TO CLEAN 18 INCHES INTO STREET | Nov 15, 2021 | Pending | — |
| 047281415Z | Jul 19, 2021 | FAILURE TO CLEAN 18 INCHES INTO STREET | Oct 18, 2021 | Pending | — |
| 0211455916 | Aug 10, 2020 | FAILURE TO CLEAN 18 INCHES INTO STREET | Nov 18, 2020 | Pending | — |
| 039014857J | Dec 26, 2019 | FAILURE TO MAINTAIN ELEVATOR OR CONVEYING SYSTEM | Feb 21, 2020 | Defaulted (did not respond) | — |
| 1484370 | Dec 26, 2019 | BRAKE MAINTENANCE TAG EXPIRED 2/7/18, CAT ONE TAG EXPIRED ON 3/21/17 | Feb 21, 2020 | Defaulted (did not respond) | — |
| 011685482N | May 16, 2019 | LABELS MARKINGS | Jul 25, 2019 | Defaulted (did not respond) | — |
| 653999 | Nov 20, 2018 | FAILURE TO COMPLY W/ COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#32092272N ISSUED ON 1/12/18, AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2). AN ACCEPTABLE CERTIFICA | Mar 22, 2019 | Found in violation | — |
| 037012383P | Nov 20, 2018 | FAIL TO COMPLY W COMMISSIONER ORDER TO FILE CERT OF CORRECTION W DOB | Mar 22, 2019 | Found in violation | — |
| 032097655N | Aug 8, 2018 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER: SERVICE EQUIPMENT - BOILER | Oct 5, 2018 | Defaulted (did not respond) | — |
| 582432 | Aug 8, 2018 | B254;50A;50B;50C:AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN.50A:"U" RATED EXPANSION TANK W/NO SAFETY RELIEF VALVE.50B:BACK FLOW PREVENTER LEAKING.50C:INSULATION MISSING & FALLING OFF HOT WATER PIPING. | Oct 5, 2018 | Defaulted (did not respond) | — |
| 616418 | May 8, 2018 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED THE FOLLOWING IN THE SPRINKLER ROOM,COMPACTOR ROOM AND ROOF RESPECTIVELY,THE INSTALLATION OF A WATER PUMB MOTOR GARBAGE COMPACTOR MOTOR AND A SPLIT AC UNIT PRICE TO OBT | Jun 29, 2018 | Defaulted (did not respond) | — |
| 035331825Z | May 8, 2018 | ELECTRICAL WORK WITHOUT A PERMIT | Jun 29, 2018 | Defaulted (did not respond) | — |
| 581457 | Jan 12, 2018 | 50. FOUND RBI BOILER MODEL CB1250 1,250,000 BTU'S INOPERATIVE DUE TO NO GAS SUPPLY. SUPPLY GAS TO BOILER & CORRECT ANY VIOLATING CONDITIONS & SUBMIT A C OF C. | Mar 2, 2018 | Settled by stipulation | — |
| 032092272N | Jan 12, 2018 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER: SERVICE EQUIPMENT - BOILER | Mar 2, 2018 | Settled by stipulation | — |
| 012071427K | Dec 13, 2017 | FIRE PROTECTION SYSTEMS:FAIL TO PREVENT UNNECESSARY UNWARRANTED ALARMS | Jul 12, 2018 | Found in violation | — |
| 011598886Y | Nov 15, 2017 | CERTIFICATES OF FITNESS AND CERTIFICATES OF QUALIFICATION | Jan 11, 2018 | Found in violation | — |
| 012068429R | Sep 14, 2017 | FIRE PROTECTION SYSTEMS:FAIL TO PREVENT UNNECESSARY UNWARRANTED ALARMS | Nov 9, 2017 | Defaulted (did not respond) | — |
| 012066411J | Jul 18, 2017 | FIRE PROTECTION SYSTEMS:FAIL TO PREVENT UNNECESSARY UNWARRANTED ALARMS | Sep 14, 2017 | Defaulted (did not respond) | — |
| 035212037X | Nov 9, 2016 | WORK WITHOUT A PERMIT | Apr 28, 2017 | Found in violation | — |
| 1231904 | Nov 9, 2016 | WORK W/O A PERMIT. GENERATOR ON SITE.NOTED: AT TIME OF INSPECTION OF 6STORY BLDG AT GRADE LEVEL IN THE REAR EXP#3 OBSERVED LARGE GENERATOR WIRED INTO PANEL AND NOT ADEQUATELY VENTED W/F() PIPE TO OUTSIDE.HEAVY | Apr 28, 2017 | Found in violation | — |
| 759586 | Oct 23, 2013 | FENCE EXCEEDS PERMITTED HEIGHT. APPROX 8FT HIGH CHAIN LINK FENCE ERECTED AROUND VACANT LOT. REMEDY: CONFORM FENCE TO CODE. | Dec 20, 2013 | Defaulted (did not respond) | — |
| 035078109L | Oct 23, 2013 | FENCE EXCEEDS PERMITTED HEIGHT | Dec 20, 2013 | Defaulted (did not respond) | — |
| 1235493 | May 6, 2003 | FAILURE TO PROVIDE A SOLID FENCE AT LEAST EIGHT FEST HIGH TO PROTECT PUBLIC DISCONTINUE CONSTRUCTION OPERATIONS REMEDY: IMMEDIATELY ENCLOSE SITE WITH FENCE AS PER CODE REQUIREMENTS | Aug 1, 2003 | Written off | — |
| 1235492 | Apr 17, 2003 | WORK W/O A PERMIT. WORK NOTED: CONSTRUCTED A THREE STORY METAL FRAME BLDG. SECTIONS OF EXTERIOR WALLS AND ROOF ARE INCOMPLETE, DEFECTIVE, RUSTED AND OPEN TO THE ELEMENTS. REMEDY:IMMEDIATELY OBTAIN NECESSARY | Jun 6, 2003 | Defaulted (did not respond) | — |
| 0129368030 | Aug 1, 2002 | FAILURE TO SWEEP 18 INCHES FROM CURB | Sep 11, 2002 | Written off | — |
| 0129364730 | Jul 25, 2002 | FAILURE TO SWEEP 18 INCHES FROM CURB | Sep 4, 2002 | Written off | — |
| 0129364676 | Jul 18, 2002 | FAILURE TO SWEEP 18 INCHES FROM CURB | Aug 28, 2002 | Written off | — |
| 0115772360 | Apr 19, 2002 | FAILURE TO SWEEP 18 INCHES FROM CURB | Jun 25, 2002 | Written off | — |
| 0120876205 | Dec 24, 2001 | FAILURE TO SWEEP 18 INCHES FROM CURB | Jan 31, 2002 | Written off | — |
| 0120876113 | Dec 13, 2001 | FAILURE TO SWEEP 18 INCHES FROM CURB | Feb 5, 2002 | Written off | — |
| 0115766943 | Jan 12, 2001 | SNOW, ICE DIRT ON SIDEWALK | Feb 22, 2001 | Written off | — |
| 0114725692 | Jun 22, 2000 | FAILURE TO SWEEP 18 INCHES FROM CURB | Aug 3, 2000 | Written off | — |
| 0109361991 | Feb 7, 2000 | FAILURE TO SWEEP 18 INCHES FROM CURB | Nov 22, 2000 | Written off | — |
| 034064049P | Nov 13, 1991 | FAILURE TO PROVIDE PROTECTION AT SIDES OF EXCAVATION. | Dec 27, 1991 | Written off | — |
| 508989 | Nov 13, 1991 | FAILURE TO PROVIDE PROTECTION AT SIDE OF EXCAVATION. APPROX. 15'SHEAR CUT SOUTH AND WEST SECTION OF SITE,WITHOUT SHEETING SHORING AND BRACINOR ANGLE REPOSE. REMEDY:PROVIDE SHEETING SHORING AND BRACING OR PROVID | Dec 27, 1991 | Written off | — |