| 1840091 | Jul 20, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:AT 1ST FL GYM EMERGENCY LIGHTS NOT WORKING WHEN TESTED THROUGHOUT VARI | Aug 10, 2026 | POP/IN-VIO | — |
| 035734794L | Jul 20, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Aug 10, 2026 | POP IN-VIOL | — |
| 1840090 | Jul 20, 2026 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:AT 1ST FL FITNESS RM#113 NOT INSTALLED/PROVIDED WITHOUT | Aug 10, 2026 | POP/IN-VIO | — |
| 1840089 | Jul 20, 2026 | REISSUE ECB#35724624J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 1ST FL SMOKE DOOR NEAR EXIT 1 DOOR IN DISREPAIR RACKED WHEN TESTED.REM:REPAIR AND/OR REPLACE. | Aug 10, 2026 | POP/IN-VIO | — |
| 035734797R | Jul 20, 2026 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS | Aug 10, 2026 | POP IN-VIOL | — |
| 035734796P | Jul 20, 2026 | FAIL MAINTAIN BLDG IN COMPLIANT MANNER:LACK EMERGENCY LIGHT FOR EXITS | Aug 10, 2026 | POP IN-VIOL | — |
| 035724624J | Sep 8, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Oct 20, 2025 | POP IN-VIOL | — |
| 035724650N | Sep 8, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Oct 20, 2025 | POP IN-VIOL | — |
| 1691193 | Sep 8, 2025 | REISSUE#35684622M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT CELLAR LEVEL(GYM.EQUIPMT.RM)AREA THE WALK AND CEILING SHOW SIGAS AT WATER PENETRATION WITH THE POOLING AND DECAYING PLASTER.REM:R | Oct 20, 2025 | POP/IN-VIO | — |
| 1677657 | Sep 8, 2025 | REISSUE#35684623Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THERE WERE SEVERAL DOORS AT SCATTERED LOCATIONS AND LEVELS,THROUGHOUT THE SCHOOL THAT WERE NOT OPERATING PROPERLY.MOSTLY FPSC UNITS. | Oct 20, 2025 | POP/IN-VIO | — |
| 0703934110 | Jun 28, 2025 | FAILURE TO PERMANENTLY RESTORE CUT WITHIN REQUIRED TIME | Sep 29, 2025 | Defaulted (did not respond) | — |
| 0703897289 | May 18, 2025 | FAILURE TO PERMANENTLY RESTORE CUT WITHIN REQUIRED TIME | Aug 25, 2025 | Defaulted (did not respond) | — |
| 0703860860 | Apr 6, 2025 | FAILURE TO PERMANENTLY RESTORE CUT WITHIN REQUIRED TIME | Jul 14, 2025 | Defaulted (did not respond) | $2,400.00 |
| 0703770569 | Dec 10, 2024 | FAILURE TO OBTAIN A CONFIRMATION NUMBER- PROTECTED STREET | Mar 17, 2025 | Defaulted (did not respond) | $750.00 |
| 0703690498 | Sep 13, 2024 | USE OPENING OF STREET W O PERMIT | Jan 27, 2025 | Pending | — |
| 1727756 | Aug 13, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED INTERIOR FIREPROOF SELF CLOSING DOORS AT 5TH FL STAIR A CAFETERIA ENTRY,3RD FL STAIR C & A,2ND FL STAIR A,1ST FL STAIR C & TWO SETS OF SMOKE DOORS BY | Oct 17, 2024 | POP/IN-VIO | — |
| 1701723 | Aug 13, 2024 | EXIT DOOR NOT SELF-CLOSING.NOTED EXTERIOR EXIT DOOR AT EXIT#2 NOT CLOSING PROPERLY.LEFT DOOR RUBS OR FRAME/SADDLE,RIGHT DOOR DOES NOT LATCH ON.REM:REPAIR/REPLACE DOOR. | Oct 17, 2024 | POP/IN-VIO | — |
| 1690271 | Aug 13, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT CELLAR LEVEL STORAGE/WORKSHOP ADJACENT TO RM#135,EVIDENT WATER PENETRATION THROUGH CEILING WITH SPALLING PLASTER.REM:REPAIR AND/OR REPLACE. | Oct 17, 2024 | POP/IN-VIO | — |
| 035684624X | Aug 13, 2024 | EXIT DOOR NOT SELF-CLOSING | Oct 17, 2024 | POP IN-VIOL | — |
| 035684622M | Aug 13, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Oct 17, 2024 | POP IN-VIOL | — |
| 035684623Y | Aug 13, 2024 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Oct 17, 2024 | POP IN-VIOL | — |
| 0703661458 | Jul 30, 2024 | STREET CLOSING WITHOUT PERMIT | Jan 27, 2025 | Defaulted (did not respond) | $5,000.00 |
| 0703662190 | Jul 30, 2024 | USE OPENING OF PROTECTED STREET WITHOUT PERMIT | Jan 27, 2025 | Defaulted (did not respond) | $5,000.00 |
| 035676335J | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 3, 2023 | POP IN-VIOL | — |
| 035676330K | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 3, 2023 | POP IN-VIOL | — |
| 035676331M | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 3, 2023 | POP IN-VIOL | — |
| 1693763 | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDIN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC1006.1; 27-381. NOTED:AT 1ST FOOR BETWEEN SMOKE DOORS AND MAIN ENTRANCE TO THE BUILDING, GYM | Nov 3, 2023 | POP/IN-VIO | — |
| 1041987 | Jul 14, 2023 | REISSUE #35654983K. NOTED: AT ROOF LEVEL, THE BULKHEAD HAS LEAKS IN VARIOUS AREAS AND IS CAUSING DAMAGE TO THE INSIDE WALLS. REMEDY: REPAIR/REPLACE. | Nov 3, 2023 | POP/IN-VIO | — |
| 167721 | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT BASEMENT STAIR A ENTRANCE AND CORRIDOR LEADING TO STAIR B, HAVE SPALLING MASONRY AND CRACKS WITH REINFORCED SHEET EXPOSED IN VARIOUS AREAS THROUG | Nov 3, 2023 | POP/IN-VIO | — |
| 167060 | Jul 14, 2023 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 5TH FLOOR CAFETERIA ENTRANCE BY ELEVATOR BANK, 4TH FLOOR ROOM 401, 409, 411, 3RD FLOOR STAIR C, 2ND FLOOR STAIR A , 1ST FLOOR STAIR A, GYMNASIUM, | Nov 3, 2023 | POP/IN-VIO | — |
| 035676332Y | Jul 14, 2023 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: ILLUMINATE EXITS | Nov 3, 2023 | POP IN-VIOL | — |
| 035654984M | May 25, 2022 | FAIL TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: USE PROB DOOR HARDWARE | Sep 15, 2022 | POP IN-VIOL | — |
| 1035197 | May 25, 2022 | REISSUE#35584121X.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE AT ROOF LEVEL THE ROOF OF THE BULKHEAD LEAKS CAUSING DAMAGE TO THE INSIDE WALLS AND CEILING OF BULKHEAD.REMEDY:REPAIR AND/OR REPLACE. | Sep 15, 2022 | POP/IN-VIO | — |
| 1631298 | May 25, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC1008.1.8;27-371.NOTE THE FOLLOWING DOORS HAVE ILLEGAL KICK STOPS INSTALLED:301,201,202,204,116,115,208.REMEDY:PROVIDE | Sep 15, 2022 | POP/IN-VIO | — |
| 1606728 | May 25, 2022 | REISSUE#35584225K.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE IN BASEMENT SUMP PUMP ROOM IN STATE OF DISREPAIR WITH OVERFLOW OF DISCHAGRE CAUSING A VERY STRONG SMELL.SMELL MAYBE A HEALTH ISSUE AS | Sep 15, 2022 | POP/IN-VIO | — |
| 035654981R | May 25, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 15, 2022 | POP IN-VIOL | — |
| 035654982Z | May 25, 2022 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Sep 15, 2022 | POP IN-VIOL | — |
| 1606730 | May 25, 2022 | REISSUE#35584123J.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC712.3;27-345.NOTE AT BASEMENT LEVEL IN BOILERROOM PIPE PENETRATE THROUGH WALLS.NO FIRE STOPPING AROUND PIPES.REMEDY | Sep 15, 2022 | POP/IN-VIO | — |
| 035654983K | May 25, 2022 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 15, 2022 | POP IN-VIOL | — |
| 1606342 | Jul 22, 2021 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER JUMP PUMP ROOM IN STATR OF DISREPAIR OVERFLOWING () AND HAS A SHEEL THAT IS VERY STRONG COMPLY WITH CODE | Nov 4, 2021 | POP/IN-VIO | — |
| 035584123J | Jul 22, 2021 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Nov 4, 2021 | POP IN-VIOL | — |
| 1606333 | Jul 22, 2021 | REISSUE ;35467093N FAILURE TO MAINTAIN BLDG COMPLAINT MANNER NO FIRESTOPPING PER BC 712:3:27-345 OBSERVED AT BOILER ROOM PENETRATIONS OBSERV THROUGH WALS WITHOUT FIRE STOPPING COMPLY WITH CODE | Nov 4, 2021 | POP/IN-VIO | — |
| 035584225K | Jul 22, 2021 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 4, 2021 | POP IN-VIOL | — |
| 1377618 | Jul 22, 2021 | REISSUE #35487091J EXIT DOOR NOT SELF CLOSING NOTED EXTERIOR DOOR RIGHT OF ENTRANCE CLOSE TO WEST DOOR RIGHT OF ENTRANCE CLOSE TO WEST WING & DOUBLE DOORS IN THAT CORRIDOR TO WEST WING GYM DOROS ALL NOT SELF CL | Nov 4, 2021 | POP/IN-VIO | — |
| 1031180 | Jul 22, 2021 | REISSUE :35487090H FAILURE TO MAINTAIN BDLG IN CODE COMPLIANT MANNER NOTED 5TH FLOOR STAIR BULKHEAD HAS WATER PENETRATION AND WATER DAMAGE COMPLY WITH CODE | Nov 4, 2021 | POP/IN-VIO | — |
| 035584121X | Jul 22, 2021 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Nov 4, 2021 | POP IN-VIOL | — |
| 035584122H | Jul 22, 2021 | EXIT DOOR NOT SELF-CLOSING | Nov 4, 2021 | POP IN-VIOL | — |
| 1604886 | Apr 21, 2021 | CLASS 1VIOLATION ISSUED 1/ NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC,REMEDY, FILE APPLICATION INSTALL DLM, 2/ ONE ARM OF BRAKE MONITORING BROKE | Jun 17, 2021 | POP/IN-VIO | — |
| 039042314L | Apr 21, 2021 | FAILURE TO MAINTAIN ELEVATOR OR CONVEYING SYSTEM | Jun 17, 2021 | POP IN-VIOL | — |
| 1615938 | May 28, 2020 | EXIT DOOR NOT SELF CLOSING. NOTE: EXIT DOOR FROM GYMNASIUM TO STAIR A & DOUBLE CORRIDOR DOORS TO WEST WING ARE NOT SELF CLOSING. REMEDY: REPAIR/REPLACE DOOR. | Sep 3, 2020 | POP/IN-VIO | — |
| 035487091J | May 28, 2020 | EXIT DOOR NOT SELF-CLOSING | Sep 3, 2020 | POP IN-VIOL | — |
| 035487092L | May 28, 2020 | EXIT DOOR NOT SELF-CLOSING | Sep 3, 2020 | POP IN-VIOL | — |
| 035487093N | May 28, 2020 | FAIL MAINTAIN BLDG COMPLIANT MANNER: NO FORE STOPPING | Sep 3, 2020 | POP IN-VIOL | — |
| 035487094P | May 28, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 3, 2020 | POP IN-VIOL | — |
| 035487095R | May 28, 2020 | FAILURE TO MAINTAIN BUILDING WALL S OR APPURTENANCES | Sep 3, 2020 | POP IN-VIOL | — |
| 035487090H | May 28, 2020 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER | Sep 3, 2020 | POP IN-VIOL | — |
| 1027182 | May 28, 2020 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE AT 5TH FL STAIR A BULKHEAD HAS WATER PENETRATION & WATER DAMAGE ON WALLS W/SPALLING PLASTER. REMEDY: REPAIR &/OR REPLACE. | Sep 3, 2020 | POP/IN-VIO | — |
| 1605943 | May 28, 2020 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTE: OBSERVED AT BOILER ROOM PENETRATIONS THROUGH WALLS W/O ANY FIRE STOPPING. REMEDY: PROVIDE/MAINTAIN FIRE STOPPING. | Sep 3, 2020 | POP/IN-VIO | — |
| 1474171 | May 28, 2020 | FAILURE TO MANTAIN BLDG WALLS OR APPURTENANCE. NOTE: OBSERVED AT FRONTOF SCHOOL TO THE LEFT OF THE MAIN ENTRANCE THE SIDEWALK HAS A LARGE CRACK & HOLE IN IT W/A POTENTIAL TO A TRIPPING HAZARD. REMEDY: REPAIR | Sep 3, 2020 | POP/IN-VIO | — |
| 1474147 | May 28, 2020 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTE AN OLD CHUTE NEAR BOILER ROOM WHERE THE FIBER COMMINICATION,CABLE(CONES)IN HAS A HEADER THAT HAS COLLAPSED & THE CEILING IN THE CHUTE HAS ALSO COLLAPSED & | Sep 3, 2020 | POP/IN-VIO | — |
| 1372965 | May 28, 2020 | EXIT DOOR NOT SELF CLOSING. NOTE: EXTERIOR DOOR,RIGHT OF ENTRANCE CLOSE TO WEST WING & DOUBLE DOORS IN THAT CORRIDOR TO WEST WING & DOOR. FROM GYM TO STAIR A GET STUCK & ARE NOT SELF CLOSING. REMEDY: REPAIR/REP | Sep 3, 2020 | POP/IN-VIO | — |
| 458363 | Mar 13, 2000 | FAILURE TO MAINTAIN BUILDING: DAMAGE CEILING AND WALLS IN STAIRWAY AT ROOF LEVEL EAST SIDE OF BLDG. BRICKS IN SAME BULKHEAD IS CRACKED. DAMAGE AND BULGING BRICK ON FRONT FACED. MASONRY OVER ENTRANCE IS CRACKED | Jun 8, 2000 | Defaulted (did not respond) | — |
| 038093750L | Jan 19, 2000 | FAILURE TO MAINTAIN ELEVATOR. | Mar 9, 2000 | Written off | — |
| 733901 | Jan 19, 2000 | 75U5,74M12,35T16. *74 REPLACE TELEPHONE IN ELEVATOR. PLACE CITY I.D. NO. ON MAIN LINE AND ON ALL EQUIP. | Mar 9, 2000 | Written off | — |