Open Class C
25
Immediately hazardous
Open Class B
48
Hazardous
Open Class A
11
Non-hazardous
Fines due
$40,000.00
Balance on OATH/ECB summonses
Permits on file
19
DOB permit records
Last activity
Jul 20, 2026
DOB record
Building health score
A composite of public indicators. Every input is a public record. See the full methodology.
F
Health score · Jul 29, 2026
Scored from the 300 most recent of 934 public records for this building
Open Class C violations
Immediately hazardous, uncertified
This building 25
Open Class B violations
Hazardous
This building 48
Heat & hot water records
Violations and complaints, last 24 months
This building 0
Unpaid penalties
OATH/ECB summonses with balance due
This building $40,000
Bedbug filings with infestations
Annual LL69 filings on record
This building 3
Tenant litigation
Open HP actions in Housing Court
This building 0
Active vacate order
HPD or FDNY order to vacate, still in effect
This building No
Unified timeline
Records from every agency, interleaved. Showing the 300 most recent of 934 records on file; the CSV below has the full history.
Jul 20, 2026
Feb 18, 2026
Feb 9, 2026
Nov 14, 2025
Sep 8, 2025
Jun 30, 2025
Feb 28, 2025
Dec 17, 2024
Dec 17, 2024
Dec 1, 2024
Oct 16, 2024
Sep 27, 2024
Aug 23, 2024
Aug 14, 2024
Jul 2, 2024
Jul 2, 2024
Jul 2, 2024
Jul 1, 2024
Jun 6, 2024
Jun 4, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
May 30, 2024
OATH / ECB summonses & fines
$40,000.00 is recorded as due across the 80 summonses below, out of $232,015.00 in penalties imposed. The city’s published records do not show whether a penalty was paid, reduced, or written off.
| 1698634 | Feb 18, 2026 | CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE, CREATING A HAZARDOUS | Oct 2, 2026 | PENDING | $1,250.00 |
| 1648953 | Dec 17, 2024 | ADJUST FLOOR STOPS. SHORTEN HOIST ROPES. REPLACE WORN GIBS WHERE NEEDE | Apr 18, 2025 | IN VIOLATION | $625.00 |
| 1648919 | Dec 17, 2024 | ADJUST FLOOR STOPS. MISALIGNED CAB MIRROR. OPERATOR COVER MISSING. WOR | Apr 18, 2025 | IN VIOLATION | $625.00 |
| 1599438 | Apr 1, 2024 | UNLAWFUL-ACTS, FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. NOTE: RESP | Jul 12, 2024 | IN VIOLATION | — |
| 1210276 | Jan 11, 2024 | AT TIME OF INSPECTION OBSERVED APT # 6K INSTATE OF DISREPAIR CONDITION | Apr 19, 2024 | IN VIOLATION | — |
| 1185325 | Dec 21, 2023 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. AS NOT | Mar 22, 2024 | IN VIOLATION | — |
| 1205680 | Jan 21, 2023 | RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE VIOL | Sep 1, 2023 | IN VIOLATION | — |
| 1637154 | Dec 9, 2022 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 8A & 9A REPORT OF CRITICAL | Sep 1, 2023 | IN VIOLATION | — |
| 1209883 | Oct 28, 2022 | EMERGENCY PHONE IN ELEVATOR NOT WORKING, ELEVATOR CAB NOT LEVEL WITH L | May 8, 2023 | IN VIOLATION | — |
| 1642270 | Aug 20, 2022 | CLASS 1 VIOLATION RECURRING, NO DOOR LOCK MONITORING INSTALLED IN THIS | May 8, 2023 | IN VIOLATION | — |
| 84481 | Dec 9, 2021 | FAILURE TO MAINTAIN BLDG EXTERIOR FACADE&APPURTENANCES NOTE:ATOI OBSER | Apr 22, 2022 | DEFAULT | — |
| 759222 | Dec 9, 2021 | AC28-302.1 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT.NOTE:ATOI EXTERIO | Apr 22, 2022 | DEFAULT | — |
| 1661117 | Nov 9, 2021 | CLASS 1 VIOLATION ISSUED. DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO | Jul 22, 2022 | IN VIOLATION | — |
| 1598780 | Oct 29, 2021 | FAILURE TO MAINTAIN EXTERIOR BLDG FACADE & APPURTENANCES. NOTE: AT THE | Feb 18, 2022 | DEFAULT | — |
| 791197 | Sep 20, 2021 | FAILURE TO PROVIDE ADEQUATE SAFETY SIDEWALK SHED WHERE REQUIRED. NOTE: | Jan 14, 2022 | DEFAULT | $25,000.00 |
| 791190 | Sep 20, 2021 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS/FACADE AND APPURTENCES. NO | Jan 14, 2022 | DEFAULT | $12,500.00 |
| 1600450 | Aug 13, 2021 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.AT EAST | Dec 10, 2021 | DEFAULT | — |
| 1654739 | Jun 16, 2021 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF | Mar 11, 2022 | IN VIOLATION | — |
| 1659477 | Jun 16, 2021 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF | Mar 11, 2022 | IN VIOLATION | — |
| 1714897 | Apr 1, 2021 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8A REPORT OF CRITICAL E | Nov 5, 2021 | DEFAULT | — |
| 871976 | Jan 26, 2021 | CLASS 1VIOLATION ISSUED NO DLM INSTALLED IN THIS CONTROLLER AS MANDATE | May 28, 2021 | DEFAULT | — |
| 1583900 | Jan 26, 2021 | CLASS 1 VIOLATION ISSUED NO DLM INSTALLED IN THIS CONTROLLER AS MANDAT | May 28, 2021 | DEFAULT | — |
| 1583833 | Jan 13, 2021 | CLASS 1 ITEM : NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS | Oct 29, 2021 | IN VIOLATION | — |
| 1399258 | Dec 20, 2018 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN N | Mar 8, 2019 | IN VIOLATION | — |
| 1593375 | Nov 14, 2018 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. BASEMENT SERVICE SWITCH: | Jan 18, 2019 | IN VIOLATION | — |
| 804725 | Nov 14, 2018 | FAILURE TO CLOSE UNUSED OPENINGS (KNOCKOUTS) IN OUTLET/PANEL BOX. BASE | Jan 18, 2019 | IN VIOLATION | — |
| 1652105 | Nov 14, 2018 | FAILURE TO GROUND ELECTRICAL SYSTEMS. BASEMENT SERVICE GROUND CONDUCTO | Jan 18, 2019 | IN VIOLATION | — |
| 982532 | May 18, 2018 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION | Jan 11, 2019 | IN VIOLATION | — |
| 937990 | Jan 16, 2018 | WORK W/O PERMIT. NOTED: AT 7TH FLOOR, APT 7F, FULL RENOVATION HAPPENED | Mar 30, 2018 | IN VIOLATION | — |
| 1522 | Jun 29, 2016 | 05N01,59U07. (05N01)DOOR RESTRICTOR BYPASSED. (59U07)MACHINE BRAKE MAI | Nov 18, 2016 | IN VIOLATION | — |
| 1172125 | Jun 29, 2016 | CEASE USE. 05J01,05N01,59U07. (05J01)CAR DOOR HAS GAP ADJUST. (05N01)D | Nov 18, 2016 | IN VIOLATION | — |
| 1172085 | Dec 29, 2015 | 42G11,07L10,67L10,08V01,16H11,28H11,32H11,70O02,30B06. 42-FUSE ARE IMP | May 20, 2016 | IN VIOLATION | — |
| 1003853 | Dec 29, 2015 | 67L10,32H11,11H07,20I11,08V01,20Q03,100M07. 67-PHONE DEFECTIVE; 32-GUI | Feb 19, 2016 | STIPULATION/IN-VIO | — |
| 549773 | Aug 19, 2010 | 08V10,24X10,05J10.(08)ELEVATOR FLOORS STOPS ARE NOT LEVEL.(05)EXCESSIV | Oct 15, 2010 | STIPULATION/IN-VIO | — |
| 759516 | Feb 24, 2010 | 32H10.10H7.17H7.32H10 TOP AND BOTTOM CAR GUIDE SHOES ARE WORN 10H7 CAR | Apr 23, 2010 | DEFAULT | — |
| 422707 | Nov 27, 2009 | FAILURE TO FILE AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIAN | Mar 17, 2010 | IN VIOLATION | — |
| 968096 | Jan 30, 2009 | FAILURE TO SUBMIT AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLI | Sep 18, 2009 | IN VIOLATION | — |
| 757155 | Nov 17, 2008 | 08V10.70O02.56Y13.56O02.98BB05 08V10ADJUST FL STOPS WERE NEED 56Y13 SE | Jan 16, 2009 | DEFAULT | — |
| 757070 | Aug 8, 2008 | 11L10.8V1.16L10. 11L CAR STATION BUTTON LIGHTS IS 8V LEVELING IS OFF 1 | Oct 3, 2008 | DEFAULT | — |
| 1093778 | Aug 8, 2008 | 97X10.97X RESTORE ELEVATOR TO SERVICE SO A FULL INSPECTION CAN BE MADE | Oct 3, 2008 | DEFAULT | — |
| 991480 | Oct 9, 2007 | 83X10. 83X10 RESTORE ELEVATOR BACK TO SERVICE SO THAT A PROPER INSPECT | Dec 7, 2007 | STIPULATION/IN-VIO | — |
| 991482 | Oct 9, 2007 | 83X10. 83X10 RESTORE ELEVATOR BACK TO SERVICE SO THAT A PROPER INSPECT | Dec 7, 2007 | STIPULATION/IN-VIO | — |
| 756865 | Oct 2, 2007 | 83X11.83-RESTORE TO SERVICE SO THAT A FULL INSPECTION CAN BE MADE BY T | Jan 18, 2008 | DEFAULT | — |
| 840990 | Oct 2, 2007 | 84L11,20L10,20L11,08V01,24L10,24I10,25I11,39P16.84-CALL FAN.20-MOLDING | Jan 18, 2008 | DEFAULT | — |
| 967722 | May 22, 2007 | 55Y13,31H11,27H11,12Q10,84L10,16L10,8V1,20I11,83I10,16T7. 84-L CAR FAN | Aug 3, 2007 | IN VIOLATION | — |
| 547424 | May 22, 2007 | 55Y13,83X10. 83/X REPAIR ELEVATOR SO A FULL INSP BY DEPT OF BLDG. | Aug 3, 2007 | IN VIOLATION | — |
| 470394 | Mar 29, 2007 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO CERTIFY/CORRECT NOV#34 | Sep 7, 2007 | DEFAULT | — |
| 1088406 | Mar 29, 2007 | RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALL | Sep 7, 2007 | WRITTEN OFF | — |
| 571440 | Jan 5, 2007 | RESIDENCE ALT FOR OCCUPANCY AS A DWELLING FOR MORE THEN THE LEGALLY AP | May 18, 2007 | IN VIOLATION | — |
| 27190 | Nov 19, 2006 | WORK W/O A PERMIT AT BASEMENT PARTITIONS FOR 1RM W/BED & PERSONAL ITEM | May 18, 2007 | IN VIOLATION | — |
| 732709 | Nov 19, 2006 | RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALL | May 18, 2007 | IN VIOLATION | — |
| 792234 | Sep 15, 2006 | 84D06/08V01/21M11/66O02/38O02/05#11/37A11/34J01.(84-D-06)PROPERLY SECU | Nov 3, 2006 | DEFAULT | — |
| 967548 | Sep 12, 2006 | HAZARDOUS.8L1/20I10/24I10/28Q3/34Q3/38O2/39O2/40W6/52H11/58Q3/39I10/85 | Dec 28, 2007 | IN VIOLATION | — |
| 18399 | Sep 6, 2006 | USE OR INSTALLATION OF MATERIALS OR EQUIPMENT WHICH DO NOT COMPLY WITH | May 18, 2007 | IN VIOLATION | — |
| 546458 | Aug 2, 2006 | 84I10/55BB05 (84-I-10) PROVIDE FAN IN ELEVATOR TO WORK (85-BB-05) 5YR | Dec 28, 2007 | IN VIOLATION | — |
| 1094524 | Aug 2, 2006 | 39I10,40W02,59Q07,84I10,85BB05. 39-I-10 MOTOR RM CEILING FAILING. WAT | Dec 28, 2007 | IN VIOLATION | — |
| 1094520 | Jun 2, 2006 | 8V1,85BB15,83L10,5L10,5L11,20I11,83L10,20Q7. 8/V LEVELING IS OFF ON 8T | Dec 28, 2007 | IN VIOLATION | — |
| 1094521 | Jun 2, 2006 | 85BB15/8V1/20Q7/20Q10/20Q10. 85/BB-NEEDS 5 YR TEST. 8/V-LEVELING IS OF | Dec 28, 2007 | IN VIOLATION | — |
| 521066 | Mar 8, 2006 | 8V1/14M7/20I11/11I11/9R9/20I11/5B10/20Q7. 20I- CAR DOOR VISION PANEL 1 | Jul 28, 2006 | DEFAULT | — |
| 521056 | Mar 8, 2006 | 5I11/3B10/14M7/8V1/20L11/9R9/5B10/20I11/20Q7 5/I CAR DOOR NEEDS REPLAC | Jul 28, 2006 | DEFAULT | — |
| 213783 | Feb 18, 2005 | 05L10/08V10/51K10/55Y10/58O02/20I10. 05L10-OSCILATES ON CLOSE AND NOT | Aug 5, 2005 | IN VIOLATION | — |
| 520891 | Mar 8, 2004 | 43R5/41G11/84M7/8V1/16B1/20I11/10M7/15I11/32O2/33O2/38O2/39O2/66O2/67O | Jul 23, 2004 | IN VIOLATION | — |
| 520890 | Mar 8, 2004 | 15M7/84M7/41G11/42I10/43H11/43H8/51H11/44H10/28B1/5B1/17H11/9H10/38P7/ | Jul 23, 2004 | IN VIOLATION | — |
| 146005 | Dec 12, 2003 | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION | May 6, 2005 | IN VIOLATION | — |
| 447417 | Aug 28, 2003 | 55Y10,43H10,03I10,06J10,33P07,03Y02,60O02,05F10,09I10,24X10,23I10,05F1 | Jan 16, 2004 | IN VIOLATION | — |
| 447415 | Aug 28, 2003 | 55Y10,58Y10,66O02,08V10. | Jan 16, 2004 | IN VIOLATION | — |
| 596151 | Jun 23, 2003 | 8V1 15I10 16L10 25L6 38O02 39Y2 39R9 33P16 41M7 56Y2 56Y10 58Y10 66O02 | Sep 5, 2003 | IN VIOLATION | — |
| 596147 | Jun 23, 2003 | 20Q03 39Y2 41M7 56Y13 83X11 20Q03=2 AND 5TH FLS 41M7=PROPERLY MARK COR | Sep 5, 2003 | IN VIOLATION | — |
| 437220 | May 27, 2003 | 08V10 83V10 07X10 12Q03 24X10 05I12 20I11 16X10 66O02 43H09 86U15 21Q0 | Sep 5, 2003 | IN VIOLATION | — |
| 447388 | May 27, 2003 | 08V10 39O02 58O02 58Y02 55Y14 38O02 38Y02 66O02 12Q03 15I11 16L10 21D0 | Sep 5, 2003 | IN VIOLATION | — |
| 416982 | Dec 11, 2002 | 18M7/39D6/62O2/79O2. 18 GLASS MISSING FROM FRAME. 39 SECURE DOWN CONTA | Jul 18, 2003 | IN VIOLATION | — |
| 416981 | Dec 11, 2002 | 3A11/62O2/31P17. 31 PROVIDE ACCESS TO HOISTWAY DOOR DROP KEY HOLE. 3 P | Jul 18, 2003 | IN VIOLATION | — |
| 323325 | Jun 10, 2002 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL NOTED BRICKWORK AT EAST AND | Sep 6, 2002 | IN VIOLATION | — |
| 447353 | Dec 14, 2000 | 3M7-05K10-5I11-14I11-17I12-18Q3-22L6-23U16-25Q2-37G12-21L11-30P17-40H1 | Feb 9, 2001 | IN VIOLATION | — |
| 447355 | Dec 14, 2000 | 3M7-8V1-17Q3-17I12-22D6-2202-23U16-48B15-53X11-57002-75U5-21L11 - CAPA | Feb 9, 2001 | IN VIOLATION | — |
| 447347 | Sep 15, 2000 | 3M7,5K10,8V1,17Q3,17I12,22D6,32Q3,39H11,35O2,50Y11,48H12,48B15,57O2,23 | Feb 2, 2001 | IN VIOLATION | — |
| 447346 | Sep 15, 2000 | 3M7,17M12,17Q3,22L6,22Y2,22O2,25Q3,23U16,31Q3,35Y2,40H11,51B7,50Y11,53 | Feb 2, 2001 | IN VIOLATION | — |
| 296065 | Jul 10, 2000 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECTS ARE: BRICK WORK AT | Aug 25, 2000 | IN VIOLATION | — |
| 447276 | Aug 17, 1992 | 14M,22D,35O,57O,74O, (74) CLEAN CAR TOP | Nov 19, 1992 | IN VIOLATION | — |
| 447275 | Aug 17, 1992 | 03M,07L,14I,22D,35O,37O,57O,74O, (03) REPLACE VENT COVER IN CAB. (07) | Nov 19, 1992 | IN VIOLATION | — |