Open Class C
2
Immediately hazardous
Open Class B
9
Hazardous
Open Class A
0
Non-hazardous
Fines due
$1,875.00
Balance on OATH/ECB summonses
Permits on file
12
DOB permit records
Last activity
May 26, 2026
DOB record
Building health score
A composite of public indicators. Every input is a public record. See the full methodology.
D
Health score · Jul 29, 2026
Scored from the 300 most recent of 442 public records for this building
Open Class C violations
Immediately hazardous, uncertified
This building 2
Open Class B violations
Hazardous
This building 9
Heat & hot water records
Violations and complaints, last 24 months
This building 0
Unpaid penalties
OATH/ECB summonses with balance due
This building $1,875
Bedbug filings with infestations
Annual LL69 filings on record
This building 2
Tenant litigation
Open HP actions in Housing Court
This building 4
Active vacate order
HPD or FDNY order to vacate, still in effect
This building Yes
Unified timeline
Records from every agency, interleaved. Showing the 300 most recent of 442 records on file; the CSV below has the full history.
May 26, 2026
May 13, 2026
May 6, 2026
May 6, 2026
May 4, 2026
May 2, 2026
Feb 24, 2026
Sep 22, 2025
Jun 30, 2025
Jun 30, 2025
Jun 30, 2025
Jun 10, 2025
Jan 27, 2025
Jan 22, 2025
Jan 13, 2025
Sep 23, 2024
Sep 23, 2024
May 23, 2024
May 9, 2024
Feb 5, 2024
Jan 12, 2024
Jan 10, 2024
Jan 4, 2024
Dec 28, 2023
Dec 21, 2023
Nov 3, 2023
Sep 24, 2023
Sep 24, 2023
Sep 24, 2023
Aug 31, 2023
OATH / ECB summonses & fines
$1,875.00 is recorded as due across the 93 summonses below, out of $121,850.00 in penalties imposed. The city’s published records do not show whether a penalty was paid, reduced, or written off.
| 1781175 | May 6, 2026 | CLASS 1: FIREFIGHTER SERVICE PHASE II INOPERATIVE. AT TIME OF INSPECTI | Aug 7, 2026 | PENDING | $1,250.00 |
| 1818611 | May 6, 2026 | CLASS 2: AT TIME OF INSPECTION, ELEVATOR DEVICE WAS NOT OPERATIONAL AN | Aug 7, 2026 | PENDING | $625.00 |
| 1789399 | Jun 30, 2025 | DURING THE INSPECTION, SIGNIFICANT STEP CRACKS WERE OBSERVED IN THE MO | Mar 26, 2026 | IN VIOLATION | — |
| 1364785 | Jan 4, 2024 | REPAIR EMERGENCY IN CAR COMMUNICATION | Mar 15, 2024 | IN VIOLATION | — |
| 1491805 | Dec 9, 2022 | CEASE VIOLATION ISSUED, RESPONDING TO A ELEVATOR 311 COMPLAINT AND FOU | Feb 17, 2023 | IN VIOLATION | — |
| 777966 | Sep 26, 2022 | RESTORE ELEVATOR SERVICE SO A FULL INSPECTION CAN BE DONE BY THIS DEPT | Feb 9, 2024 | IN VIOLATION | — |
| 1592640 | Apr 25, 2022 | CLASS 1 VIOLATION ISSUED, RTS, UPON INSPECTION, THE DEVICE IS FOUND TO | Jun 17, 2022 | IN VIOLATION | — |
| 1506386 | May 11, 2020 | DEFECTIVE WIRING NEAR BURNER, PETROMETER NOT FASTENED TO WALL-CORROSIO | Jul 17, 2020 | DEFAULT | — |
| 1484451 | Aug 27, 2019 | ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUP | Oct 18, 2019 | Resolved | — |
| 1322259 | Apr 10, 2018 | CU-05A10,CU-02X10; 67X10, CU-16J10; 39O02. 05A10-CAR DOOR RESTRICTO | Jun 1, 2018 | IN VIOLATION | — |
| 1260074 | Dec 21, 2017 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.NORTH E | Feb 16, 2018 | Resolved | — |
| 1319380 | Dec 21, 2017 | FAILURE TO TAKE AND PROVIDE SAFETY MEASURES TO PROTECT AND SECURE PUBL | Feb 16, 2018 | Resolved | — |
| 1396143 | Oct 4, 2016 | 1L10,5J1,10H11,16J1,17H11,56Y2,56Y13,40D6,70O2,71L10,67L10. EMERGENCY | Nov 18, 2016 | IN VIOLATION | — |
| 1322221 | Jul 25, 2016 | 97X10 RESTORE ELEVATOR TO SERVICE. | Nov 4, 2016 | IN VIOLATION | — |
| 1194377 | Jan 20, 2016 | 97X10 DEVICE 0/0/0. RETURN TO SERVICE. | Mar 18, 2016 | IN VIOLATION | — |
| 768242 | Mar 6, 2013 | B251:15M07,41W07,59M07,60Q03,67X10,70O02,71X10,99BB05.41W07:PROVIDE LO | May 6, 2013 | IN VIOLATION | — |
| 1110175 | Mar 6, 2013 | B251:70O02,97X10.97X10:REPAIR ELEVATOR & RETURN TO SERVICE SO THAT A C | May 3, 2013 | IN VIOLATION | — |
| 768235 | Mar 6, 2013 | B251:19M07,40P16,67X10,70O02.19M07:PROVIDE BOTTOM SAFETY RETAINER FOR | May 6, 2013 | IN VIOLATION | — |
| 1109847 | Dec 29, 2010 | 97X10)REPAIR/RESTORE TO SERVICE SO THAT PROPER INSPECTION MAY BE PERFO | Mar 30, 2011 | IN VIOLATION | — |
| 1109842 | Dec 29, 2010 | 97X10)REPAIR/RESTORE TO SERVICE SO THAT PROPER INSPECTION MAY BE PERFO | Mar 25, 2011 | IN VIOLATION | — |
| 1109848 | Dec 29, 2010 | 97X10)REPAIR-RESTORE TO SERVICE SO THAT PROPER INSPECTION MAY BE PERFO | Mar 25, 2011 | IN VIOLATION | — |
| 1109850 | Dec 29, 2010 | 11I10,05M07,21M07,03I07,67L10,41D06,15M07,16I10,40O02,39O02,70O02.(11I | Mar 25, 2011 | IN VIOLATION | — |
| 865527 | Sep 16, 2009 | 44H10.52H11.98BB5.70O2.39O2 | Nov 6, 2009 | STIPULATION/IN-VIO | — |
| 1050627 | Sep 16, 2009 | 44H10.52H11.98BB5.70O2.39O2 | Feb 19, 2010 | IN VIOLATION | — |
| 865528 | Sep 16, 2009 | 44H10.52H11.98BB5.70O2.39O2 | Nov 6, 2009 | STIPULATION/IN-VIO | — |
| 1109260 | Nov 28, 2008 | 11I10 24X10 29B1 39Q7 52H11 57J10 70K10 71X10 11I10 FIREMENT SERVICE L | Jan 30, 2009 | IN VIOLATION | — |
| 1109259 | Nov 28, 2008 | 52O02 CLEAN HOIST ROPES OR REPLACE | Jan 30, 2009 | IN VIOLATION | — |
| 1109257 | Nov 28, 2008 | 97X10 ENTIRE DEVICE OUT OF SERVICE REPAIR AND CALL DOB FOR A FULL INSP | Jan 30, 2009 | IN VIOLATION | — |
| 1109256 | Nov 28, 2008 | 97X10 97-ENTIRE DEVICE OUT OF SERVICE REPAIR AND CALL DOB FOR A FULL I | Jan 30, 2009 | IN VIOLATION | — |
| 864043 | Feb 20, 2008 | 83X0. 83/X. REPAIR ELEVATOR SO A FULL INSPECTION CAN BE MADE. | Jun 13, 2008 | IN VIOLATION | — |
| 864037 | Feb 20, 2008 | 11I10,27H11,12Q10,8V1,20I10,20I10. 11/I CAR STATION DAMAGED. 27/H. CAR | Jun 13, 2008 | IN VIOLATION | — |
| 666580 | Feb 20, 2008 | 20I10,27H11,24L10,11I10,8V1. 20/I. CAR DOOR VISION PANEL IS DAMAGED. 2 | Jun 13, 2008 | IN VIOLATION | — |
| 666558 | Feb 20, 2008 | 12L10,27H11,24L10,83L10,9I10,83L10. 12/L. CAR LIGHTING IS DEFECTIVE. 2 | Jun 13, 2008 | IN VIOLATION | — |
| 863659 | Jul 6, 2007 | 43H10/51H11/20M7/84L10/.20M7-VISION GLASS MISSING IN CAR DOOR PROVIDE | Jan 18, 2008 | IN VIOLATION | — |
| 863669 | Jul 6, 2007 | 43H10/51H11/84L10/.84L10-INTERCOM IN CAB NOT WORKING PROVIDE WORKING I | Jan 18, 2008 | IN VIOLATION | — |
| 603877 | Jul 3, 2007 | 83X10,66O02.83X10-RETURN ELEVATOR TO SERVICE FOR PROPER INSPECTION OF | Sep 10, 2007 | DISMISSED | — |
| 776836 | Jul 3, 2007 | 31H11,84M07,66O02.31H11-REPAIR GUIDE ROLLER WHERE NEEDED.ELEVATOR BOUN | Sep 10, 2007 | IN VIOLATION | — |
| 863632 | Jul 3, 2007 | 84L10,20M07,40T07,43H08.84L10-REPAIR EMERGENCY PHONE INSIDE ELEVATOR.2 | Sep 10, 2007 | IN VIOLATION | — |
| 863610 | Jul 3, 2007 | 83X10,59Q03,63U15,66O02,58L10.83X10-RETURN TO SERVICE.59Q03-PROVIDE LI | Sep 10, 2007 | IN VIOLATION | — |
| 863597 | Mar 9, 2007 | 20I11,12Q03,05L10,24L10,15M07.20I-CAR VISION PANEL.12Q-CAR LIGHT UNGUA | May 4, 2007 | STIPULATION/IN-VIO | — |
| 863581 | Mar 9, 2007 | 20I11,11L10,24L10,31L10,15M07,23L10.20I-CAR DOOR VISION PANEL.11L-CAR | May 4, 2007 | STIPULATION/IN-VIO | — |
| 863549 | Mar 9, 2007 | 83L10,31H11,09I10,15M07,23L10,84L10,05L10.83L-ELEVATOR SHAKES WHEN TRA | May 4, 2007 | STIPULATION/IN-VIO | — |
| 666061 | Mar 9, 2007 | 09I11,11L10,24L10,31H11,15M07,23I11.9I-CAR FLOOR IS DAMAGED.11C-CAR BU | May 4, 2007 | STIPULATION/IN-VIO | — |
| 1000839 | Sep 26, 2006 | 10H11. 10- CHANGE WORN CAR DOOR GIBS. | Jan 19, 2007 | WRITTEN OFF | — |
| 665992 | Sep 26, 2006 | 20-I-11/20-REPLACE DAMAGED CAR DOOR VISION GLASS PANEL | Jan 19, 2007 | Resolved | — |
| 720713 | Jun 13, 2006 | 58Q3,84X10,86U5. 84-REPAIR COMMUNICATION(PHONE IN CAR) | Oct 27, 2006 | WRITTEN OFF | — |
| 1057941 | Jun 13, 2006 | 83X10,51O2,38O2,86U5.DO NOT RESTORE ELEVATOR TO THE PUBLIC BEFORE A FU | Jul 28, 2006 | WRITTEN OFF | — |
| 720438 | Jun 13, 2006 | 51O2,58Q3,83X10,86U5. 51-CLEAN HOIST CABLES TO PERFORM A BETTER INSP. | Oct 27, 2006 | WRITTEN OFF | — |
| 1057954 | Jun 13, 2006 | 51O2,55X13,57X10,58Q3,86U5,84I10,84X10. 84-REPAIR MOTOR ROOM WINDOWS,G | Jul 28, 2006 | WRITTEN OFF | — |
| 665865 | Mar 14, 2006 | 83X10. REPAIR RESTORE & PROVIDE SERVICE SO A FULL INSP. COULD BE DONE | Oct 27, 2006 | IN VIOLATION | — |
| 665846 | Mar 14, 2006 | 83X10. REPAIR, RESTORE & PROVIDE SERVICE SO A FULL INSP. COULD BE DONE | Oct 27, 2006 | IN VIOLATION | — |
| 1074561 | Jan 30, 2006 | FAILURE TO FILE AN AMENDED FIFTH ROUND REPORT ACCEPTABLE TO THIS DEPAR | Jan 26, 2007 | WRITTEN OFF | — |
| 666033 | Jan 9, 2006 | 41G11/51O2/58Q3. | Feb 24, 2006 | IN VIOLATION | — |
| 666024 | Jan 9, 2006 | 83X10/41G11. | Feb 24, 2006 | IN VIOLATION | — |
| 863532 | Jan 9, 2006 | 41G11/58Q3/55Y13/55O2. | Feb 24, 2006 | IN VIOLATION | — |
| 666019 | Jan 9, 2006 | 41G11/49Q3/84X10/39O2. 84-X-10- COMMUNICATION- PHONE NOT WORKING: REPA | Oct 27, 2006 | IN VIOLATION | — |
| 1037425 | Nov 28, 2005 | FAILURE TO FILE AN AMENDED FIFTH ROUND REPORT ACCEPTABLE TO THIS DEPT. | Jan 26, 2007 | IN VIOLATION | — |
| 863453 | Sep 13, 2005 | 83X10. 83-REPAIR RESTORE AND PROVIDE SERVICE. | Jan 23, 2006 | IN VIOLATION | — |
| 880978 | Jul 27, 2005 | BQ9/36. BOILER | Sep 16, 2005 | WRITTEN OFF | — |
| 880911 | Jul 27, 2005 | BQ9/34A/36/50. NEW BOILER-BQ9. 50-HOLES IN CEILING. | May 26, 2006 | IN VIOLATION | — |
| 1006035 | Sep 10, 2004 | 83X10 83- RESTORE TO SERVICE SO A COMPLETE INSPECTION COULD BE DONE BY | Oct 22, 2004 | WRITTEN OFF | — |
| 1006036 | Sep 10, 2004 | 83X10 83- RESTORE TO SERVICE FOR A COMPLETE INSPECTION BY THIS DEPARTM | Oct 22, 2004 | WRITTEN OFF | — |
| 716558 | Dec 5, 2003 | FAILURE TO SUBMIT A FIFTH ROUND TECHINCAL REPORT:PERIODIC INSPECTION | Nov 19, 2004 | WRITTEN OFF | — |
| 198633 | Sep 24, 2003 | 03I10/04P07/12I10/30P07/16F10/84D06/49Q03/55Y10/84T07/39O02/38O02/35Q0 | Sep 17, 2004 | WRITTEN OFF | — |
| 198509 | Sep 24, 2003 | 58Q03/84D06/49Q03/51O02/39O02/38O02/28Q03/30P07/35Q03/21Q03/33O02/51H1 | Sep 17, 2004 | WRITTEN OFF | — |
| 198569 | Sep 24, 2003 | 49Q03/58Q03/51O02/39O02/38O02/28Q03/51H10/35Q03/39Y02/03I10/66O02/30P0 | Sep 17, 2004 | WRITTEN OFF | — |
| 198730 | Sep 24, 2003 | 03I10/04P07/12I10/09I10/16F10/30P07/84D06/43H10/55Y10/49Q03/35Q03/39O0 | Sep 17, 2004 | WRITTEN OFF | — |
| 0127024729 | Mar 2, 2002 | DIRTY SIDEWALK | Apr 4, 2002 | DEFAULT | — |
| 863167 | Dec 17, 2001 | 46Y2-73X11-37M7-57Z2-57O2-34M7-30O1-14M7 73=RESTORE ELEVATOR TO SERVIC | Feb 1, 2002 | WRITTEN OFF | — |
| 664299 | Nov 19, 2001 | 3I11-74#11-74I11-57O2. 3-DAMAGE CAR PANEL 74-DIRECTIONAL BELOW DOES NO | Jan 4, 2002 | WRITTEN OFF | — |
| 863153 | Nov 19, 2001 | 5#1-8V1-14M7-57O2. 5-CAR DOOR DOES NOT OPEN FULLY 8-NOT LEVEL WITH LAN | Nov 22, 2002 | WRITTEN OFF | — |
| 865477 | Nov 19, 2001 | 57O2-73X11. 57-PIT DIRT 73-RESTORE DEVICE TO HAVE A FULL INSPECTION BY | Nov 22, 2002 | WRITTEN OFF | — |
| 664296 | Nov 19, 2001 | 8V1-10#11-14M7-57O2-74#11. 8-NOT LEVEL WITH LANDING 10-LATE ON CAR LOC | Jan 4, 2002 | WRITTEN OFF | — |
| 0122313694 | Nov 4, 2001 | DIRTY SIDEWALK | Jan 10, 2002 | Pending | — |
| 1057607 | May 29, 2001 | 23 X 11, 23-RESTORE ELEVATOR TO BE INSPECTED NY THE DEPT OF BUILDING | Jul 20, 2001 | WRITTEN OFF | — |
| 863145 | May 29, 2001 | 73 X 11, 23-RESTORE ELEVATOR FOR A PERODIC INSPECTION BY THE DEPT OF | Jul 26, 2002 | IN VIOLATION | — |
| 863097 | May 25, 2001 | 74 O 2, 74 X 11, 57 O 2, 8 V 1, 20 # 11, 74-TOP OF CAR DIETYARD OIL LE | Jul 26, 2002 | WRITTEN OFF | — |
| 863122 | Apr 18, 2001 | 30Y2-3L10-4L11-50Y14-40L11-73O2-54T16-36T16-36L11-74X11-21X11-11B7-8O2 | Jun 1, 2001 | DEFAULT | — |
| 954342 | Jan 18, 2001 | FAILURE TO PROVIDE 10"X12" ELEVATOR LANDING SIGN OF FLOOR 2,3,4,5, AND | Mar 9, 2001 | WRITTEN OFF | — |
| 862709 | Nov 30, 1998 | 73X11,3I11,12I11,35P17. 73-MAKE REPAIRS & RESTORE TO SERVICE FOR FULL | Jan 22, 1999 | DEFAULT | — |
| 862704 | Aug 13, 1998 | 44U16,57O02,52Q03,10I12,21I11,30O02,35D02,03I11,. 52- BRAKE COOLING CO | Sep 25, 1998 | DEFAULT | — |
| 862690 | Aug 13, 1998 | 35D,03I,13I,21I,57O,03O,30O,16H,10I, 21-DIRECTIONAL. | Sep 25, 1998 | DEFAULT | — |
| 862702 | Aug 13, 1998 | 54U16,31Q03,10I12,03I11,11Q03,21I11,32Q03,30O02,57O02,25Q03,32Q02,16H1 | Sep 25, 1998 | DEFAULT | — |
| 862707 | Aug 13, 1998 | 03I11,10I11,35D06,57O02,21I11,30O02,52Q03,. 21- DIVIDIONAL. 52- BRAKE | Sep 25, 1998 | DEFAULT | — |
| 662635 | Jun 17, 1996 | 02X 11Q 37G 54# PROVIDE A FUSED MAN SWITCH. 36T | Aug 23, 1996 | WRITTEN OFF | — |
| 662632 | Jun 17, 1996 | 11I11, 11Q3, 31Q3, 57O2, 22D6. UNGUARD HOISTWAY WIRING. | Aug 23, 1996 | WRITTEN OFF | — |
| 662609 | Jun 17, 1996 | 74A PROVIDE A PROPER HANDRAIL 54# PROVIDE A FUSED MAIN SWITCH 44I REPA | Aug 23, 1996 | WRITTEN OFF | — |
| 862567 | Jun 17, 1996 | 50Y 74A Q 18J 74A PROVIDE TO E GUARD | Aug 23, 1996 | WRITTEN OFF | — |
| 662549 | Jun 19, 1991 | 35O,37B,37M,40B,50Y,73X,(37)REPAIR CONTROLLER,REMOVE PAPER FROM RELAYS | Apr 30, 1992 | IN VIOLATION | — |
| 862483 | Jun 19, 1991 | 40B,50Y,35O,73X,37B,37M,(40)PROVIDE PROPER TAG ON GOVERNOR (37)REPAIR | Apr 30, 1992 | IN VIOLATION | — |
| 862421 | Jan 17, 1991 | 73X,40#,73 RESTORE ELEVATOR TO SERVICE FOR PROPER INSPECTION OO40 PERF | Apr 19, 1991 | IN VIOLATION | — |
| 662535 | Jan 17, 1991 | 74X,40#,74 RESTORE ELEVATOR TO SERVICE AND PERFORM 5YR TEST FOR PROPER | Apr 19, 1991 | IN VIOLATION | — |
| 662523 | Jan 17, 1991 | 73X,40#,73 RESTORE ELEVATOR SERVICE FOR PROPER INSPECTION 40 PERFORM 5 | Apr 19, 1991 | IN VIOLATION | — |