| 1714364 | Jul 24, 2026 | NOTE: AT TIME OF INSPECTION, I OBSERVED SIDEWALK SHED ERECTED AT EXPOU | Oct 1, 2026 | PENDING | $2,400.00 |
| 1798982 | Jul 14, 2026 | CLASS 1 C/U: BRAKE SWITCH MONITOR INOPERATIVE - THE SWITCHES DISABLED | Sep 17, 2026 | PENDING | $1,250.00 |
| 1052206 | Apr 20, 2026 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTI | Jul 23, 2026 | PENDING | $3,125.00 |
| 1767043 | Oct 1, 2025 | CLASS 1 CEASE USE ITEMS: 1)DOOR ZONE RESTRICTOR INOPERATIVE. 2)DLM INO | Jan 15, 2026 | IN VIOLATION | $1,250.00 |
| 1029332 | Jul 28, 2025 | OBSERVED IN THE BASEMENT INCORRECT SPRINKLER HEADS INSTALLED AND ONE S | Sep 29, 2026 | DEFAULT | $6,250.00 |
| 1693028 | Jul 28, 2025 | CEASE USE ITEM: BRAKE SHOES HAVE EXCESSIVE GAP AND NEED TO BE CORRE CT | Oct 20, 2026 | DEFAULT | $6,250.00 |
| 1693034 | Jul 28, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED MISSIN | Oct 20, 2026 | DEFAULT | $6,250.00 |
| 1030310 | Jul 28, 2025 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPIN | Sep 29, 2026 | DEFAULT | $12,500.00 |
| 1027680 | Jul 28, 2025 | I FOUND A FEDERAL FST70 BOILER WITH OIL PUMP ON ALL THE TIME/AIR FAN P | Sep 29, 2026 | DEFAULT | $6,250.00 |
| 1028318 | Jul 28, 2025 | PROVIDE THE OVERHEAD DOOR TO BE SELF LOCKING AND CLOSING. | Sep 29, 2026 | DEFAULT | $3,125.00 |
| 1799371 | Jul 28, 2025 | CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEA | Sep 29, 2026 | DEFAULT | $6,250.00 |
| 1789495 | Apr 8, 2025 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL E | Jul 3, 2025 | DEFAULT | $10,000.00 |
| 1215229 | Aug 12, 2024 | I OBSERVED ON ALL FLOORS THE ELECTRICAL CLOSETS WITHOUT PROPER ILLUMIN | May 23, 2025 | IN VIOLATION | $800.00 |
| 1215025 | Aug 12, 2024 | I OBSERVED IN THE BASEMENT THE BOILER ROOM DISCONNECT MADE INACCESSIBL | May 23, 2025 | IN VIOLATION | $1,600.00 |
| 1215518 | Aug 12, 2024 | I OBSERVED IN STAIRWAY"D" THE INSTALLATION OF A CIRCUIT BREAKER PANEL | May 23, 2025 | IN VIOLATION | $800.00 |
| 1214694 | Aug 12, 2024 | OBSERVED PAINTED SPRINKLER HEADS THROUGHOUT BUILDING AS WELL AS SPRINK | May 8, 2025 | IN VIOLATION | $625.00 |
| 1214870 | Aug 12, 2024 | I OBSERVED THE ELECTRICAL CLOSETS ON FLOORS 3, 6, 9, &12 NOT DEDICATED | May 23, 2025 | IN VIOLATION | $1,200.00 |
| 1727520 | Aug 12, 2024 | I OBSERVED THE INSTALLATION OF ELECTRIC PANELS, BRANCH CIRCUIT WIRING, | Dec 5, 2024 | IN VIOLATION | $4,800.00 |
| 1727510 | Aug 12, 2024 | I OBSERVED IN THE BASEMENT BOILER ROOM AND IN THE ELEVATOR "E" MOTOR R | Dec 5, 2024 | IN VIOLATION | $2,400.00 |
| 1430168 | Aug 12, 2024 | OBSERVED NO FRESH AIR VENTILATION IN THE GAS METER ROOM LOCATED IN THE | Aug 14, 2025 | IN VIOLATION | $1,250.00 |
| 1727545 | Aug 12, 2024 | I OBSERVED IN THE ELECTRICAL CLOSETS ON ALL FLOORS, THROUGHOUT THE BAS | Dec 5, 2024 | IN VIOLATION | $800.00 |
| 1727514 | Aug 12, 2024 | I OBSERVED IN THE WATER METER ROOM, THE WATER METER JUMPER HANGING AND | Dec 5, 2024 | IN VIOLATION | $4,800.00 |
| 1672648 | Aug 12, 2024 | OBSERVED NEWLY INSTALLED PIPING TO GAS METERS LOCATED AT BASEMENT/CELL | Aug 14, 2025 | IN VIOLATION | — |
| 1727373 | Aug 9, 2024 | SECURE ROPE INSIDE WINDING DRUM FROM MOVEMENT. CLEAN AND REPAIR OIL LE | Dec 5, 2024 | IN VIOLATION | $625.00 |
| 1727369 | Aug 9, 2024 | BRAKE SWITCHES BYPASSED. THIS IS A SAFETY FEATURE WHICH ENSURES PASSEN | Dec 5, 2024 | IN VIOLATION | $1,250.00 |
| 1727480 | Aug 9, 2024 | DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSUR | Dec 5, 2024 | IN VIOLATION | $1,250.00 |
| 1788195 | Jun 28, 2024 | OBSERVED ON THE GROUND FLOOR IN BOOTH 3 IN NEW YORK ONE JEWELRY REFINE | Sep 11, 2025 | IN VIOLATION | $625.00 |
| 1764964 | Jan 16, 2024 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 8C REPORT INDICATING CORRECTI | Apr 25, 2024 | IN VIOLATION | $1,250.00 |
| 1572102 | Jun 29, 2022 | FAILURE TO MAINTAIN BUILDING FACADE AND APPURTENANCES. NOTE:OBSERVED A | Nov 17, 2022 | IN VIOLATION | — |
| 1219902 | Apr 26, 2022 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES.NOTED:A | Dec 8, 2022 | IN VIOLATION | — |
| 1564752 | Oct 8, 2021 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE8C REPORT INDICATING CORRECTIO | Feb 24, 2022 | DEFAULT | $6,250.00 |
| 1356206 | Sep 1, 2021 | FOUND EMERGENCY STOP SWITCH INSIDE CAR IS NOT WORKING. CEASE USED. REP | Mar 10, 2022 | ADMIT/IN-VIO | — |
| 1480616 | Apr 13, 2021 | GAS PIOLIT REGULATOR MISSING VENT LIMITER+SPRING COVER/OIL TANK SIGN M | Aug 19, 2021 | IN VIOLATION | — |
| 1480639 | Apr 13, 2021 | FLUE DOOR GASKETS DEFECT/FLUE TO CHIMNEY BASE HAS SOOT/CHIMNEY BASE DO | Aug 19, 2021 | IN VIOLATION | — |
| 1000328 | Jul 10, 2019 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES: AS NOTE | Sep 24, 2020 | IN VIOLATION | — |
| 1145854 | May 25, 2016 | UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 2 | Jul 14, 2016 | IN VIOLATION | — |
| 1020255 | Feb 26, 2015 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS, | Apr 16, 2015 | IN VIOLATION | — |
| 785279 | Oct 1, 2009 | FAIL TO COMPLY W.COMM ORDER TO FILE A CERTIFICATE OF CORRECTION W/DOB | Aug 26, 2010 | IN VIOLATION | — |
| 645749 | May 8, 2009 | WORK W/O PERMIT WORK NOTED AT CELLAR LVL EXP#1 FRONT ERECT WOOD AND ST | Oct 29, 2009 | IN VIOLATION | — |
| 645770 | May 8, 2009 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NO FIRESTOPPING AND | Oct 29, 2009 | IN VIOLATION | — |
| 645758 | May 8, 2009 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER DEFECTS NOTED AT CEL | Oct 29, 2009 | IN VIOLATION | — |
| 978457 | Mar 27, 2009 | SUPERVISION OR USE OF RIGGING EQUIPMENT W/O A RIGGER'S LICENSE. NOTED: | May 14, 2009 | IN VIOLATION | — |
| 739828 | Jun 5, 2002 | ALTERED BUILDING OCCUPIED WITHOUT A VALID C OF O 3 ROOMS OCCUPIED IN 2 | Jul 26, 2002 | STIPULATION/IN-VIO | — |
| 353372 | Jul 3, 2001 | PLUMBING WORK WITHOUT A PERMIT. ALL THE BATHROOMS FIXTURES AND PIPES | Aug 23, 2001 | IN VIOLATION | — |
| 326080 | May 30, 2001 | 46 H 10, 46 K 10, 57 O 02, RENEW HOISTCABLES | Sep 5, 2001 | STIPULATION/IN-VIO | — |