| 1149557 | Sep 21, 2009 | FAILURE TO FILE AN ACCEPTABLE 6 ROUND TECHNICAL REPORT IN COMPLIANCE W | Dec 17, 2009 | WRITTEN OFF | — |
| 1215505 | Mar 27, 2009 | WORK W/O A PERMIT. NOTED: FENCE ERECTED UNDER APPL #110042864 PERMIT E | May 14, 2009 | WRITTEN OFF | — |
| 1263938 | Feb 20, 2009 | WORK WITHOUT A PERMIT; EXPIRED PERMIT. ERECTED CONST FENCE APPROX 7'UN | Apr 22, 2010 | WRITTEN OFF | — |
| 903388 | Nov 11, 2008 | FAILURE TO MAINTAIN WEATHER PROOF INTEGRITY OF ADJOINING PROPERTY UPON | Mar 3, 2011 | IN VIOLATION | — |
| 639778 | Nov 3, 2008 | WORK W/O OUT A PERMIT EXPIRED NOTED PLYWOOD CONSTRUCTION FENCE ERECTED | Apr 16, 2009 | DEFAULT | — |
| 1217768 | Sep 25, 2008 | FAILURE TO FILE AFFIDAVITS AND/OR COMPLY WITH OTHER REQUIREMENTS SET 4 | Apr 16, 2009 | WRITTEN OFF | — |
| 799391 | Jan 24, 2008 | EXPIRED PERMIT FOR FENCE UNDER ALT#104592353 PERMIT EXPIRED 12/31/07. | Mar 13, 2008 | IN VIOLATION | — |
| 663448 | Oct 2, 2007 | FAILURE TO PROVIDE WEATHER PROOFING INTEGRITY OF ADJOINING BLDG. NOTE | Aug 14, 2008 | IN VIOLATION | — |
| 663199 | Jun 6, 2007 | SE.27-1026(2D)FAILURE TO PROVIDE WEATHER PROOFING INTEGRITY OF ADJOINI | Aug 14, 2008 | IN VIOLATION | — |
| 720574 | Mar 21, 2007 | EXPIRED PERMIT.(SHED)NOTED:DEMO AT 2,3FL,SHED UP PERMIT #104532542 EXP | Sep 27, 2007 | IN VIOLATION | — |
| 826676 | Dec 5, 2003 | FAILURE TO INSTALL AN ACCEPTABLE TWO-WAY VOICE COMMUNICATION SYSTEM WI | Jan 29, 2004 | DEFAULT | — |
| 523753 | Nov 28, 2003 | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION | Mar 4, 2004 | DEFAULT | — |
| 807079 | Sep 19, 2003 | EXIT LIGHTING DEFECTIVE/ FAILS TO MEET BUILDING CODE STANDARDS. DEFECT | Dec 4, 2003 | DEFAULT | — |
| 521361 | Sep 19, 2003 | NO FIRE ENCLOSURE FOR BOILER. NOTED: BLOCK WALLS WHERE DOORS WERE PRES | Dec 4, 2003 | DEFAULT | — |
| 679811 | Sep 19, 2003 | FAILURE TO MAINTAIN BIULDING HAZARDOUS. NOTED: BROKEN CEILING TILES, L | Dec 4, 2003 | DEFAULT | — |
| 679807 | Sep 19, 2003 | FAILURE TO MAINTAIN BIULDING. NOTED: IN CELLAT DISLODGED CONCRETE, EXP | Dec 4, 2003 | DEFAULT | — |
| 823262 | Sep 19, 2003 | EXIT SIGN DEFECTIVE. ALL EXISTS SIGNS ARE INOPERABLE ON THE 4TH, 5TH, | Dec 4, 2003 | DEFAULT | — |
| 235021 | Sep 19, 2003 | EXIT PASSAGEWAY OR CORRIDOR: TOTAL OBSTRUCTION. NOTED: ALL PASSAGEWAYS | Dec 4, 2003 | DEFAULT | — |
| 807076 | Sep 19, 2003 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. NOTED: FIRE ESCAPE IS SEVE | Dec 4, 2003 | DEFAULT | — |
| 807038 | May 20, 2003 | FAILURE TO MAINTAIN BUILDING.NOTED DISLODGED CONCRETE,EXPOSING REBAR I | Aug 7, 2003 | DEFAULT | — |
| 807039 | May 20, 2003 | NO FIREPROOF ENCLOSURE FOR BOILER.NOTED:BLOCK WALLS WHERE DOORS WERE P | Aug 7, 2003 | DEFAULT | — |
| 807033 | May 20, 2003 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL.NOTED:MISSING & PARTIALLY D | Feb 19, 2004 | DEFAULT | — |
| 520380 | Mar 28, 2003 | FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT: PERIODIC INSPECTION | Jul 3, 2003 | DEFAULT | — |
| 807024 | Feb 19, 2003 | FAILURE TO MAINTAIN EXTERIOR BLDG WALL. NOTED:SEVERLY CORRODED FIRE ES | Jun 5, 2003 | DEFAULT | — |
| 679707 | Feb 19, 2003 | FAILURE TO MAINTAIN BLDG. NOTED:CIRCUIT BOXES, ELECTRICAL WIRES, BX CA | Jun 5, 2003 | DEFAULT | — |
| 232421 | Feb 19, 2003 | NO FIRE PROOF ENCLOSURE FOR BOILER.NOTED:DOORS AND ADJACENT WALLS REMO | Jun 5, 2003 | DEFAULT | — |
| 232515 | Feb 19, 2003 | EXIT LIGHTING DEFECTIVE/FAILS TO MEET BLDG CODE STANDARDS. NOTED:NO PR | Jun 5, 2003 | DEFAULT | — |
| 807032 | Feb 19, 2003 | FAILURE TO PROVIDE STAIR SIGNS IN AN OFFICE BLDG.NOTED:FLOOR SIGNAGE M | Jun 5, 2003 | DEFAULT | — |
| 806970 | Jul 15, 2002 | NO FIRE PROOF ENCLOSURE FOR BOILER. NOTED: AT CELLAR LEVEL BOILER ROOM | Sep 26, 2002 | DEFAULT | — |
| 679423 | Jul 15, 2002 | FAILURE TO MAINTAINT BLDG. NOTED EXPOSED ELECTRICAL WIRES AT VARIOUS L | Sep 26, 2002 | DEFAULT | — |
| 806967 | Jul 15, 2002 | FAILURE TO MAINTAIN EXTERIOR BLDG WALL. NOTED: MISSING AND UNSTABLE ST | Sep 26, 2002 | DEFAULT | — |
| 806968 | Jul 15, 2002 | EXIT LIGHTING DEFECTIVE/FAILS TO MEET BLDG CODE STANDARDS. NOTED: NO O | Sep 26, 2002 | DEFAULT | — |
| 679476 | May 2, 2002 | FAILURE TO INSTALL AN ACCEPTABLE TWO WAY VOICE COMMUNICATION SYSTEM WI | Jan 30, 2003 | DEFAULT | — |
| 679459 | Oct 25, 2001 | FAILURE TO INSTALL AN ACCEPTABLE TWO-WAY VOICE COMMUNICATION SYSTEM WI | Jan 3, 2002 | DEFAULT | — |
| 679301 | Aug 11, 2001 | FAILURE TO INSTALL AN ACCEPTABLE TWO WAY VOICE COMMUNICATION SYSTEM WI | Oct 18, 2001 | DEFAULT | — |
| 678465 | Jul 28, 2000 | FAILURE TO INSTALL AN ACCEPTABLE TWO-WAY COMMUNICATION SYSTEM WITH | Nov 9, 2000 | DEFAULT | — |
| 826510 | Jul 26, 1999 | FAILURE TO INSTALL AN ACCEPTABLE 2-WAY VOICE COMMUNICATION SYSTEM WITH | Jan 25, 2000 | IN VIOLATION | — |
| 677872 | Jan 8, 1999 | FAILURE TO INSTALL AN ACCEPTABLE TWO WAY VOICE COMMUNICATION SYSTEM | Mar 11, 1999 | DEFAULT | — |
| 677850 | Mar 9, 1998 | FAILURE TO INSTALL AN ACCEPTABLE 2-WAY VOICE COMMUNICATION SYSTEM W/ | Oct 15, 1998 | IN VIOLATION | — |
| 179578 | Jul 8, 1997 | 50O75U40U73X57O53B35U 73-PROPERLY REPAIR DEVICE & PLACE IN WORKING | Jan 15, 1998 | IN VIOLATION | — |
| 179807 | Jul 8, 1997 | 35O40U57O53B73X35U 40-PERFORM & FILE 5YR. TEST 73-PROPERLY REPAIR DEVI | Jan 15, 1998 | IN VIOLATION | — |
| 179475 | Jul 8, 1997 | 35O50O53B75B11B15J57O35M40U 75-NO CITY TAGS ON EQUIPMENT 40 PERFORM | Jan 15, 1998 | IN VIOLATION | — |
| 826299 | Jun 3, 1997 | FAILURE TO INSTALLED AN ACCEPTABLE TWO WAY VOICE COMMUNICATION SYSTEM | Jul 24, 1997 | WRITTEN OFF | — |
| 130235 | Oct 25, 1995 | FAILURE TO SUBMIT A THIRD ROUND TECHNICAL REPORT PERIODIC INSPECTION O | Mar 14, 1996 | IN VIOLATION | — |
| 588588 | May 13, 1994 | FAILURE TO SUBMIT ATHIRD ROUND TECHNICAL REPORT; PERIODIC INSPECTION O | Jun 30, 1994 | WRITTEN OFF | — |
| 43366 | Dec 21, 1990 | FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84 CERTIFYING | May 23, 1991 | IN VIOLATION | — |